Testing new batteries, Hp t1500j, and hp t1500 g3 models, see figure 24 – HP Tower Uninterruptible Power System User Manual

Page 29

Advertising
background image

UPS MAINTENANCE

HP T750 G2, HP T750J, HP T1000 G3, HP T1000J, HP T1500 G3, and HP T1500J UPS Models User Guide

S 505922-002

22

4

5

3

Cable Retainer

Figure 24

Removing the Battery (HP T1000J, HP T1500J, HP T1500 G3 Models)

6

Replace the battery. See “Recycling the Used Battery or UPS” on page 23 for
proper disposal.

7

Place the new battery pack in the same position with the battery terminals at the
top.

8

Connect the black battery cable to the new battery.

9

Slide the batteries into the UPS. For HP T1000J, HP T1500 G3, and HP T1500J,
carefully replace the black battery cable into the cable retainer.

C

A

U

T

I

O

N

To avoid damage to the battery leads, be sure that the cables do not bind against the
guide rail while reinstalling the battery.

10

Connect the red battery cable.

NOTE:

A small amount of arcing may occur when connecting the batteries. This is normal

and does not damage the unit or present any safety concern.

11

Replace the metal battery cover and UPS front bezel.

 Testing New Batteries

NOTE:

Allow batteries to charge for 6 to 24 hours before testing.

NOTE:

The batteries must be fully charged and the UPS must not be in Battery mode to

perform the self‐test.

Press and hold the

(Test/Alarm Reset) button for three seconds to initiate a self-test.

The 15-second test automatically distributes the load to the battery and tests the battery's
performance. While the test is in progress, the indicators cycle through and the UPS
beeps. When complete, the UPS returns to Normal mode as indicated by the



(Power On) indicator.

If there is a problem with the battery, the UPS beeps, the

+ -

(On Battery) indicator

illuminates and the

(Service) indicator flashes. Check the battery connections and be

sure the battery is fully charged. Call your service representative if the problem persists.