HP Tower Uninterruptible Power System User Manual

Page 32

Advertising
background image

SPECIFICATIONS

HP T750 G2, HP T750J, HP T1000 G3, HP T1000J, HP T1500 G3, and HP T1500J UPS Models User Guide

S 505922-002

25

Table 6

Electrical Output

100V Models

120V Models

230V Models

Power Levels (rated at nominal
inputs)

100V: 750 VA, 500W

1000 VA, 680W
1200 VA, 980W

110V and 120V: 750 VA, 500W

1000 VA, 670W

120V: 1400 VA, 950W

750 VA, 500W

1000 VA, 670W
1400 VA, 950W

Power Factor

0.67

Regulation (Normal mode)

-10% to +6% of nominal voltage

Regulation (Battery mode),
Nominal Voltage ±5%

Same as selected nominal input

voltage

100V

Same as selected nominal input

voltage

110V, 120V

Same as selected nominal

input voltage

220V, 230V, 240V

Voltage Waveform

Sine wave

Overcurrent Protection

Inverter saturation current limited

Output Receptacles

HP T750J, HP T1000J, and

HP T1500J: (6) 5-15

HP T750 G2: (4) 5-15

HP T1000 G3 and HP T1500 G3:

(6) 5-15

HP T750 G2:

(4) 10A, IEC-320

HP T1000 G3 and HP

T1500 G3: (6) 10A, IEC-320

Table 7

Environmental and Safety

100/120V Models

230V Models

Operating Temperature

Up to 1,500 meters: 0°C to 40°C (32°F to 104°F); UL tested 25°C (77°F)

Above 1,500 meters: 0°C to 35°C (32°F to 95°F)

Transit/Storage Temperature

-15°C to 55°C (5°F to 131°F)

Relative Humidity

5–95% noncondensing

Operating Altitude

Up to 3,000 meters above sea level

Audible Noise

Less than 45 dBA typical

Surge Suppression

ANSI C62.41 Category A (formerly IEEE 587)

Safety Conformance

UL 1778 2nd Edition; UL 497A;

CSA C22.2, No. 107.1

IEC/EN 62040-1-1 and IEC/EN 60950-1

Safety Markings

cULus, cUL, NOM-NYCE

CE, TÜV, C-Tick, GOST R, EK, IRAM, TISI

EMC (Class B)

FCC Part 15, ICES-003, VCCI

IEC/EN 62040-2, FCC Part 15, ICES-003, VCCI