HP Tower Uninterruptible Power System User Manual

Page 33

Advertising
background image

SPECIFICATIONS

HP T750 G2, HP T750J, HP T1000 G3, HP T1000J, HP T1500 G3, and HP T1500J UPS Models User Guide

S 505922-002

26

Table 8

Battery

UPS Configuration

HP T750 G2: (2) 12V, 7 or 7.2 Ah internal batteries

HP T750J and HP T1000 G3: (2) 12V, 9 Ah internal batteries

HP T1000J, HP T1500 G3, and HP T1500J: (3) 12V, 9 Ah internal batteries

Voltage

HP T750 G2, HP T750J, and HP T1000 G3: 24 Vdc

HP T1000J, HP T1500 G3, and HP T1500J: 36 Vdc

Type

Sealed, maintenance‐free, valve‐regulated, lead‐acid

Charging

Advanced charging for faster recovery; approximately 3 hours to 90% usable capacity at nominal line

and no supplementary power supply load

Monitoring

Advanced monitoring for earlier failure detection and warning

Table 9

Battery Runtimes (in Minutes)

UPS Models by VA Ratings

Load (VA)

Watts

750

1000

1400

200

128

38

41

58

300

192

27

28

41

500

320

14

15

28

600

402

9

10

19

750

503

6

8

14

900

603

6

10

1000

670

5

8

1200

804

6

1400

938

5

NOTE Battery times are approximate and may vary depending on the load configuration and battery charge.