Hardware options installation 51

The BIOS suspends the server for 5 minutes if it detects a cautionary temperature level. If the
cautionary temperature level is still detected after 5 minutes, the BIOS performs an orderly
shutdown and then restarts. This process repeats until the cautionary temperature level is no
longer detected.

The BIOS performs an orderly shutdown if the following minimum requirements are not met: a
minimum of five fans in the standard configuration or seven fans in the redundant configuration.

The server performs an immediate shutdown if it detects a critical temperature level.

IMPORTANT: An immediate shutdown is a hardware-controlled function and it overrides any firmware or

software actions.

In the operating system:

With the Health Driver loaded and Thermal Shutdown enabled in RBSU, the Health Driver
performs an orderly shutdown if it detects a cautionary temperature level. If the server detects a
critical temperature level before the orderly shutdown occurs, the server performs an immediate
shutdown. Additionally, the Health Driver performs an orderly shutdown if the following minimum
requirements are not met: a minimum of five fans in the standard configuration or seven fans in
the redundant configuration.

With the Health Driver loaded and Thermal Shutdown disabled in RBSU, the server performs an
immediate shutdown if it detects a critical temperature level.

Without the Health Driver loaded, the server performs an immediate shutdown if it detects a
critical temperature level.

IMPORTANT: An immediate shutdown is a hardware-controlled function and it overrides any firmware or

software actions.

Installation requirements

WARNING: To reduce the risk of electric shock, personal injury, and damage to the

equipment:

Do not attempt to service any parts of the equipment other than those specified in the

following procedure. Any other activities may require that you shut down the server
and remove the power cord.

Installation and maintenance of this product must be performed by individuals who

are knowledgeable about the procedures, precautions and hazards associated with
the product.

You must observe the following requirements when installing redundant hot-plug fans:

To ensure optimum cooling, populate the primary fan locations, 2, 4, 5, 6, and 7, before populating
the redundant locations.

If a primary fan fails, replace the nonfunctioning fan before installing fans in redundant locations.