9. Position and fasten the inner wall plate to the inside wall

using an appropriate fastener for the specific wall

construction. Apply silicone sealant between the inner

wall plate and the inside wall.

10. Make certain the 5” telescoping pipe has been fully

engaged onto the 5 inch elbow. Drill two 1/8” holes 180°

apart at the junction of the two joints. Secure with four

#8 sheet metal screws and apply silicone sealant to the

seams. Make sure all the 5” pipe joints are sealed including

the joint to the collar on the water heater’s air supply box

(See Figure 9).

4. Extend the 3” telescoping pipe to its maximum length.

Place the smaller section onto the 3” elbow at least 1 and

1/2 inches (See Figure 9). Drill two holes 180° apart

and secure with the two #8 sheet metal screws provided.

Apply silicone sealant to the joint.

5. Attach the larger section of the 5” telescoping pipe to the

flange on the outer wall plate (See Figure 9). Drill holes

90° apart with a 1/8” drill bit and fasten with four #8 sheet

metal screws (provided). Apply silicone sealant to the

seam.

6. Extend the 5” telescoping tube to its maximum length.

From outside of the building, insert a 5” tube/outer wall

plate assembly through the opening in the exterior wall

and onto the 5” elbow (See Figure 9). Seat the base of

the outer wall plate onto the exterior wall. Apply silicone

sealant between the plate and the exterior wall.

Figure 9: Vertical Installation

3” Pipe

Inner Wall

Plate

Screws

& Sealant

3” Telescoping

Pipe

Wall

7. Place the 3” tube located in the vent cap into the end of

the 3” telescoping tube (See Figure 10). Drill two holes

180° apart with a 1/8” drill bit and secure with two #8

sheet metal screws. Apply sealant to the joint. Seat the

cap against outer wall plate with the word “HOT” in an

upright position.

8. Secure the vent cap/outer wall plate assembly to the

exterior wall with the four 1 and 1/2” screws provided

(See Figure 10). Varying wall structures may require a

different type of screw anchor. To prevent rain from

entering the water heater vent pipe, the 5” tube should

be sloped downward towards the wall 1/4” per foot.

Figure 10: Vertical Installation

5” Elbow

Inner Wall

Plate

Screws

& Sealant

3” Telescoping

Pipe

5” Telescoping Pipe

Outer Wall Plate

Inner Wall

Plate

Screws

& Sealant

Outer

Wall

Plate

HOT

Screws

Vent Cap

Screws

Sealant

Slope down 1/4”

per foot

Optional Vertical Extension Kit

Installations requiring dimension "A" to be greater than 62.75”

(40 Gallon) or 71.00” (50 Gallon) will require the use of the

optional vertical extension kit. The maximum height of the

"A" dimension cannot exceed 98 inches. If the "A" dimension

for your application is less than 98 inches, you will have to

cut the 3 and 5 inch pipes in the vertical extension kit to the

correct length. For example, if your applicable "A" distance

is 80 inches, then 98 inches - 80 inches = 18 inches. Therefore,

you will need to cut 18 inches from both the 3 and 5 inch

vertical extension pipes. DO NOT CUT THE CRIMPED END

OF THE 5 INCH PIPE.

After cutting both the pipes to the proper size, place the 3”

vertical extension pipe over the flue pipe reducer on the

upper air box and press it firmly downward until seated. Using

a level, make sure the extension tube is pointing straight up.

Drill 4 holes 90° apart with a 1/8” drill bit and fasten with four

#8 sheet metal screws (provided). Apply silicone sealant to

the seam.

Place the uncrimped end of the 5 inch extension pipe over

the 3 inch extension pipe and seat it onto the collar on the

air box. Making sure the 3 inch extension pipe is centered

in the 5 inch pipe, drill four holes 90° apart with the 1/8” drill

bit and fasten with four #8 sheet metal screws (provided).

Apply silicone sealant to the seam. Place the flared end of

the 3 inch elbow over the 3 inch extension pipe and press

it firmly downward until seated. Drill four holes 90° apart with

the 1/8” drill and fasten with four #8 sheet metal screws

(provided). Apply silicone sealant to the seam.

Install the 5 inch elbow over the 3 inch elbow and seat it

down onto the crimped end of the 5 inch extension pipe.

Temporarily place the 5 inch telescoping pipe onto the 5 inch

elbow and adjust it to give a 1/4 inch per foot downward

slope to the outside wall. Secure the 5 inch elbow to the

extension pipe by drilling four holes 90° apart with the 1/8”

drill and inserting four #8 sheet metal screws. Apply silicone

sealant to the joint. Place the inner wall cover plate over the

5 inch elbow. This plate will be positioned later. Proceed to

step 4.