Figure 4: vent cap termination locations – American Water Heater 6510238 User Manual

Page 6

Advertising
background image

6

The Vent terminal is HOT when the water heater is in

operation. Do not touch the vent terminal or place any object

where contact with the vent terminal may occur. A protective

louvered wall or fence is recommended when the hot vent

cap is low enough to be touched accidentally (see Figure 5).

A Vent guard kit (Kit # 6907245) may be ordered by contacting

the manufacturer of this water heater at 1-800-999-9515.
• The exhaust outlet must not terminate under a patio, deck,

or any covered area.

• Do not terminate the exhaust outlet near walkways or into

alleys or other publicly accessible areas.

• Do not locate the vent terminal too close to shrubs or

bushes.

• Caulk all cracks, seams, and joints within 6 feet horizontally

above and below the vent.

• Do not terminate the vent within 12 inches of any other

direct vented appliance vent

HOT

Hot Vent Cap

Protective Louvered

Wall or Fence

Figure 5: Protective Louvered Wall or Fence

3 feet Min.

Figure 4: Vent Cap Termination Locations

A. 12 in (30 cm) min. clearance above grade, veranda,

porch, deck, balcony, or maximum anticipated snow

level.

B. 9 in (23 cm) min. clearance on top and side of window

or door that may be opened. Do not install below a

window or door that may be opened.

C. Clearance to permanently closed window.**
D. 12 in (30 cm) min vertical clearance to ventilated soffit.
E. 12 in (30 cm) min. clearance to unventilated soffit.
F. Clearance to outside corner **

U.S. Installation

**Clearance in accordance with local installation codes and the requirements of the gas supplier

G. 12 in (30 cm) min. clearance to inside corner formed

by two exterior walls.

H. 4 ft (122 cm) min. clearance to each side of center line

extending above meter/regulator assembly.

I. 4 ft (122 cm) min. clearance to service regulator vent

outlet.

J. 12 in (30 cm) min. clearance to nonmechanical air

supply inlet to building or the combustion air inlet to

any other appliance.

K. 3 ft (91 cm) above if within 10 ft (3 m) horizontally of

mechanical air supply inlet.