THROUGH THE ROOF VENTING*

1. Center the heater directly under the roof opening.

This vent system must be installed vertically only.

2. All the pipes needed to assemble the vent are included

in the kit. Do not add to the length of the vent system.

The total height is limited to 15 feet on a 50-gallon

heater (See Figure 11). The 40-gallon heater is 8

and1/4” shorter. The total 15-foot height must stick

through the roof a minimum of 2 feet. If the height

needed is less than 15 feet, determine the height

needed and subtract that from 15 feet. That amount

needs to be cut off one of the 3” pipes and 5” pipes.

Cut the non-flared end of the 3” pipe and the uncrimped

end of the 5” pipe.

3. Assemble the kit from the top down starting with the

termination. Attach a 3” pipe using 4 #8 sheet metal

screws 90° apart and seal the joint with sealant. Then

attach the 5” section in the same manor. Drill 1/8”

pilot holes for the screws. Continue until the full length

is assembled. Put the telescoping 5” section on last.

4. Place the heater in position, feed the vent assembly

down through the roof with the flashing in place, and

allow it to rest with the 3” pipe attached to the 3” vent

terminal on the heater. Use screws and sealant to

secure that joint. Extend the 5” telescoping section to

connect to the 5” termination on the heater. Secure

that joint with screws. Seal that joint and the sliding

joint with silicone to make an airtight assembly.

5. Secure the flashing and vent assembly to the roof.

(*Through the Roof Venting Kit available from manufacturer)

Roof Jack Assembly

8 Ft. Min.
15 Ft. Max

Roof Flashing

Secure All

Connections

with Screws

and Apply

Silicone

Sealant

Figure 11: Through the Roof Venting

2 Ft. Min.

From Any Object

within A 10 Foot

Horizontal Radius