Vent pipe system, Combustion air supply and ventilation, Through the wall venting – American Water Heater 6510238 User Manual

Page 9

Advertising
background image

9

Important: Air for combustion and ventilation must not

come from a corrosive atmosphere. Any failure due to

corrosive elements in the atmosphere is excluded from

warranty coverage.

Vent Pipe System

This is a direct vent water heater which draws its combustion

air from outside of the structure and exhausts all products

of combustion to the outside of the structure.

Through-the-wall installations require locating the water

heater next to an outside wall. All necessary components

are supplied for the standard through-the-wall installation.

Optional vertical and horizontal extension kits are available

for installations that exceed the standard horizontal and

vertical distances (see table at right). Only one vertical and

one horizontal kit can be used on the same installation.

Through the Wall Venting

1. Make sure a proper location has been selected for the

water heater installation. Consider the following:

· Water piping
· Gas Piping
· Access for service
· Proper clearance for combustibles
· Drainage for the temperature and pressure relief

valve and drain pan.

· Vent cap termination

2. Determine the “A” dimension for your specific water heater

by referencing figure 7. Cut a 6 inch opening through the

wall in the location as shown. Determine the location of

electrical wiring, pipes, or wall studs before cutting.

NOTE: Installations requiring an “A” dimension (vertical

height) greater than what is shown as standard in the table

will require the use of a vertical extension kit (See “Vertical

Install Kit” on Page 10).

3. If you are not using the vertical extension kit, place the

3” elbow on the flue pipe reducer on the air box and point

it in the desired direction (See Figure 8). Press it firmly

downward until seated. Drill 4 holes 90° apart with a 1/8”

drill bit and fasten the four #8 sheet metal screws provided.

Apply silicone sealant to the joint. Install the 5” elbow

over the 3” elbow and seat it into the collar on the air box.

Drill 4 holes 90° apart with a 1/8” drill bit and fasten the

four #8 sheet metal screws provided. Apply silicone

sealant to the joint. Place the inner wall cover plate over

the 5” elbow. This plate will be positioned later.

Figure 7: “A” & “B” Dimensions

Figure 7: “A” & “B” Dimensions

KIT

CAPACITY

40 GALLON

50 GALLON

“A”

“B”

“A”

“B”

62.75”

62.75”

62.75 - 89.75”
62.75 - 89.75”

15.75 - 24.50”
27.00 - 38.00”
15.75 - 24.50”
27.00 - 38.00”

STANDARD
HORIZONTAL
VERTICAL
BOTH

71.00”

71.00”

71.00 - 98.00”
71.00 - 98.00”

15.75 - 24.50”
27.00 - 38.00”
15.75 - 24.50”
27.00 - 38.00”

Figure 8: Vertical Installation

3” Elbow

Screws &

Sealant

1

2

5” Pipe

3” Elbow

Inside Cover

Plate

Screws

& Sealant

“B”

“A”

Combustion Air Supply and

Ventilation

NOTE:

1. Dim. “A” measured from center of cutout to bottom of heater.

2. Dim. “B” measured from center of heater to outside of wall.