Water system piping, Piping installation, Figure 12: water piping installation – American Water Heater 6510238 User Manual

Page 12: Figure 13: typical tempering valve installation

Advertising
background image

Water System Piping

Piping Installation

Piping, fittings, and valves should be installed according

to the installation drawing (Figure 12). If the indoor

installation area is subject to freezing temperatures, the

water piping must be protected by insulation.
Water supply pressure should not exceed 80% of the

working pressure of the water heater. The working

pressure is stated on the water heater’s data plate. If

this occurs a pressure limiting valve with a bypass may

need to be installed in the cold water inlet line. This

should be placed on the supply to the entire house in

order to maintain equal hot and cold water pressures.
Important: Heat cannot be applied to the water fittings

on the heater as they may contain nonmetallic parts. If

solder connections are used, solder the pipe to the

adapter before attaching the adapter to the hot and cold

water fittings.
Important: Always use a good grade of joint compound

and be certain that all fittings are drawn up tight.
1.

Install the water piping and fittings as shown in

Figure 12. Connect the cold water supply

(3/4 NPT) to the fitting marked “C”. Connect

the hot water supply (3/4 NPT) to the fitting

marked “H”.

Important: Some models may contain energy saving

heat traps to prevent the circulation of hot water within

the pipes. Do not remove the inserts within the heat

traps.
2.

The installation of unions in both the hot and

cold water supply lines is recommended for

ease of removing the water heater for service or

replacement.

3.

The manufacturer of this water heater recommends

installing a tempering valve or an anti-scald device

in the domestic hot water line as shown in Figure

13. These valves reduce the point of use

temperature of the water by mixing cold and hot

water and are readily available for use. Contact

a licensed plumber or the local plumbing authority.

4.

If installing the water heater in a closed water

system, install an expansion tank in the cold water

line as specified under “Closed System/Thermal

Expansion” (Page 13).

5.

Install a shut-off valve in the cold water inlet line.

It should be located close to the water heater and

be easily accessible. Know the location of this

valve and how to shut off the water to the heater.

6.

Install a temperature and pressure relief valve in

the opening marked “Temperature and Pressure

(T & P) Relief Valve” on the water heater. Add a

discharge line to the opening of the T & P relief

valve. Follow the instructions under Temperature

and Pressure Relief Valve" (Page 14).

7.

After piping has been properly connected to the

water heater, remove the aerator at the nearest

hot water faucet. Open the hot water faucet

and allow the tank to completely fill with water. To

purge the lines of any excess air, keep the hot

water faucet open for 3 minutes after a constant

flow of water is obtained. Close the faucet and

check all connections for leaks.

In a Closed System Use

a Thermal Expansion Tank

Pressure Reducing

Valve with Bypass

Main

Water

Supply

Cold Water

Inlet Valve

Hot Water

Outlet

Union

Temperature and

Pressure Relief Valve

Discharge Line

6 Inches Maximum

Above Drain

Drain Line

3/4 Inch ID

Minimum

Drain

Metal

Drain Pan

1 3/4 Inch Depth Max.

1 Inch

Min.

Massachusetts: Install a

vacuum relief in cold water

line per section 19 MGL 142.

Figure 12: Water Piping Installation

Follow the tempering

Valve manufacturer’s

Instructions

Cold

Water

Inlet

Hot

Water

Outlet

Tempered

water to fixtures

Tempering Valve

(Set to 120°F)

Figure 13: Typical Tempering Valve Installation

Figure 13: Typical Tempering Valve Installation

12

Cold Water Supply

to Fixtures

Advertising