AGS Functional Test
Before any further programming, confirm that the generator is working properly. Using the generator’s
own controls, manually turn it on and then shut it off.
Next, test the remote start functionality by using the MATE3’s
Generator Status
screen.
Figure 144 AGS Functional Test
The AGS test confirms the AGS function works and the generator has been operated during the AGS
programming.
IMPORTANT:
It is important not to confuse AGS with Gen Alert.
These are two separate
methods for requesting a generator to start. Gen Alert set points should not be
used as AGS set points.
To test the AGS function through the MATE3:
1. Press
the
GEN hot key to bring up the
Generator Status
screen.
2. Press
the
<ON> soft key and wait for the generator to start running.
3. Press
the
<OFF> soft key to shut the generator off.
4. Press
the
<AUTO> soft key to put the generator in AUTO mode.
5. Press
the <BACK> soft key to return to the Home screen.