Electrical Installation: Top Cable Entry

10

Symmetra MW 1000 kW 480 V Installation - 990-4112E

Battery cable connections (top cable entry)

WARNING!
Make sure that the battery breakers are open (OFF) prior to running the cables.

CAUTION!
Refer to the battery manufacturer’s installation manual.

CAUTION!
The minimum DC voltage rating of the battery supply over-current protective device is
500 V.

Note

Over-current protection for the battery circuit is required by code.

Note

BAT 1 and BAT 2 cables MUST be run in separate conduits.