Required Breaker Settings

The Symmetra

®

MW is a fault-tolerant system capable of handling and surviving overloads and

internal/external faults. The overload performances and fault clearings are possible when the system
meets specified minimum requirements for breaker settings. The settings are specified in the tables
below, but some of them can also be found in the Electrical Specification section. The settings are all
minimum settings and may not result in a drop-out.

Input and upstream breakers — minimum settings

Output and downstream breakers — minimum settings

See also

See separate guide on parallel operation for information on required breaker settings in
parallel systems.

Q1, Q5, and any upstream breaker

Duration [S]

Current [A]

Total load [%]

Event/Operation

< 0.005

18 kA

--

Internal fault clearing

1880*

130

Overload on-line

1245

100

On-line

1370

110

On-line + Max. Battery

Charge

* Only applicable to Q1

Q2, Q4, Q6, and any downstream breaker

Duration [S]

Current [A]

Total load [%]

Event/Operation

< 0.005

18 kA

--

Internal fault clearing.

60

2406*

200

Overload on-line

600

1504*

125

Overload on-line

1203

100

On-line

* Only applicable to Q2 and Q4