Specifications: Low-Impedance/High-Impedance Grounding

28

Symmetra MW 1000 kW 480 V Installation - 990-4112E

From an external grounding resistor, and through a separate conduit, connect a cable to the output
circuit grounding bar.

Note

For high-impedance grounding, the installation must include ground-fault detection
circuitry.