Specifications: Electrical Specification
30
Symmetra MW 1000 kW 480 V Installation - 990-4112E
AC Input
AC Input
DC Input
CAUTION!
AC and DC disconnect switches and over-current protection must be included in the
installation.
Note
All wiring must comply with all applicable national and/or local electrical codes.
Note
Max. prospective RMS short-circuit current on input terminals: 200 kA
Max. prospective RMS short-circuit current on battery terminals: 50 kA
AC Input
Input Rating
1000 kW/kVA
Power Factor
1
Input Voltage
480 V
Input Frequency
60 Hz
Nominal Input Current (note 1)
1240 A
Maximum Input Current (note 2)
1364 A
Input Current Limitation (note 3)
1564 A
Recommended Cable per phase (notes 4, 6, 7, a, b, c)
5 × 500 kcmil
DC Input
Nominal Voltage (note 5)
2 x 384 V
I
Nom
Discharge (note 8)
1356 A
I
Max
Discharge (note 9)
1595 A
Recommended cable (per pole)
5 × 500 kcmil
CAUTION!
The minimum DC voltage rating of the battery supply over-current protective device is
500 V.