PROGRAM PRESETS & COUNTER LOAD VALUE MODULE

The Preset and Counter Load values are accessed from any of the

indication displays, or from any of the main menus in the programming loop,
by pressing the PRS key. The top line shows the Preset number and the
display that it is assigned to (C

Count, R

Rate). The following flowchart

shows only the Preset and Counter Load portion:

PRESETS VALUES

Preset values P1 through P6 activate solid state outputs 01 SNK through

06 SNK respectively, when the assigned display value equals the preset
value. Presets P1 to P4 are assigned to the count display, and preset 5 & 6 can
be assigned to either the count or rate display. The output action (Timed,
Latched, or Boundary) is programmed in the Program Outputs Module. The
preset values may range from 99,999 to 999,999.

The Count Scale Factor, will have a direct effect on the preset value being

entered, if the output (preset) is assigned to the count display. For a Scale
Factor Value greater than “1”, the preset value should be a whole number
multiple of the Scale Factor value. If it is not, the Legend will automatically
adjust the preset value up or down to force it to be evenly divisible by the
Scale Factor.

COUNTER LOAD VALUE

The Counter Load value (CL) allows the user to change the count value.

The count display will reset to the counter load value if the reset mode is set to
counter load (In the Program Counter Module). The counter load value can be
programmed from 99999 to 999999.