A.C. POWER WIRING

The AC power is connected to the bottom left terminals 1 & 2 marked AC

PWR. The voltage selector switch, located at the side of the unit, is used to
select the proper voltage. The switch is a slide movement type and can be set
by using a small screwdriver. If the switch is toward the front of the unit, it is
set for 115 VAC input. If the switch is towards the rear of the unit, it is set for
230 VAC input. The switch will be in the 230 VAC position when shipped
from the factory.
Note: Before applying power to the unit make sure the A.C. power switch is set

for the proper voltage setting.
To reduce the chance of noise spikes entering the AC line and affecting the

unit, the AC power should be relatively “clean” and within the specified

±10% variation limit. Connecting power from heavily loaded circuits or
circuits that also power loads that cycle on and off, (contactors, relays,
motors, etc.) should be avoided.

DC POWER WIRING

The DC power is connected to the bottom left terminals 3 & 4 marked +12

VDC and common. The DC power source must be capable of supplying the
unit’s rated current (250 mA) and be within the specified +20% variation
limit. It is not necessary to provide battery backup to retain programmable
information. The Legend has nonvolatile memory and information is stored
on power down (Refer to block diagram).

SERIAL COMMUNICATIONS

Refer to the RS 485 Serial Communications section of the manual, for

wiring and operational procedures.

USER INPUT WIRING

Programmable external user inputs are digital inputs that are active when

connected to TBC #3 Common. The use of shielded cable is recommended.
Follow the EMC Installation Guidelines for shield connection.