Once the Number of Count Edges (NCE) to be used has been determined,

the Remaining Scaling factor required, “K

R

”, can be calculated. This is the

Total Scaling Factor, “K

T

”, divided by the Number of Count edges used as

shown in Formula #2:

FORMULA #2: K

R

K

T

÷

NCE

WHERE:

K

R

= Remaining Scaling Factor.

K

T

= Total Scaling Factor.

NCE = Number of Count Edges.

In our original example, the Total Scaling Factor, “K

T

” was determined to

be 0.041667. Since this value is less than one, sufficient pulse information is
being generated, i.e., there is enough resolution for the units selected. The
Number of Count edges can be left at the factory set value of X1. The Total
Scaling Factor, “K

T

”, therefore equals the Remaining Scaling Factor, “K

R

”.

K

R

0.041667

÷

1

0.041667

If the remaining scaling is between 0.6000 and 5.9999, it can be

programmed directly into the Scale Factor value and the X1 factory setting
for the Count Scale Multiplier “SCM”, can be used.

COUNT SCALE MULTIPLIER

The general rule for choosing an SCM value is, when the Remaining

Scaling Factor, “K

R

”, is less than 0.6000, an SCM value of 0.1 or 0.01 can be

used to get a Scale Factor value between 0.6 and 5.9999 or to the point where
the maximum number of significant digits is obtained.

FORMULA #3: SF

K

R

÷

SCM

WHERE:

SF = Count Scale Factor.
K

R

= Remaining Scaling Factor.

SCM = Count Scale Multiplier.

Following our continuing example, it is easy to see that the Remaining

Scaling Factor, “K

R

” (0.041667), cannot fit into the Scale Factor Value

without losing significant digits. Using the Formula above and a Scale
Multiplier value of 0.01 will allow us to get the maximum number of
significant digits possible for the Count Scale Factor value:

SF

K

R

÷

SCM

0.041667

ч

0.01

4.1667

-52-