Red Lion LEGEND User Manual

Page 42

Advertising
background image

EMC INSTALLATION GUIDELINES

Although this unit is designed with a high degree of immunity to

ElectroMagnetic Interference (EMI), proper installation and wiring methods
must be followed to ensure compatibility in each application. The type of the
electrical noise, source or coupling method into the unit may be different for
various installations. The unit becomes more immune to EMI with fewer I/O
connections. Cable length, routing and shield termination are very important
and can mean the difference between a successful or a troublesome
installation. Listed below are some EMC guidelines for successful
installation in an industrial environment.

1. Use shielded (screened) cables for all Signal and Control inputs. The shield

(screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in
order of their effectiveness.
a. Connect the shield only at the panel where the unit is mounted to earth

ground (protective earth).

b. Connect the shield to earth ground at both ends of the cable, usually

when the noise source frequency is above 1 MHz.

c. Connect the shield to common of the unit and leave the other end of the

shield unconnected and insulated from earth ground.

2. Never run Signal or Control cables in the same conduit or raceway with AC

power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are
long and portable two way radios are used in close proximity or if the
installation is near a commercial radio transmitter.

3. Signal or Control cables within an enclosure should be routed as far away

as possible from contactors, control relays, transformers, and other noisy
components.

4. In extremely high EMI environments, the use of external EMI suppression

devices, such as ferrite suppression cores, is effective. Install them on
Signal and Control cables as close to the unit as possible. Loop the cable
through the core several times or use multiple cores on each cable for
additional protection. Install line filters on the power input cable to the unit
to suppress power line interference. Install them near the power entry point
of the enclosure. The following EMI suppression devices (or equivalent)

are recommended:
Ferrite Suppression Cores for signal and control cables:

Fair Rite # 0443167251 (RLC #FCOR0000)
TDK # ZCAT3035 1330A
Steward #28B2029 0A0

Line Filters for input power cables:

Schaffner # FN610 1/07 (RLC #LFIL0000)
Schaffner # FN670 1.8/07
Corcom #1VB3
Corcom #1VR3

Note: Reference manufacturer’s instructions when installing a line

filter.

5. Long cable runs are more susceptible to EMI pickup than short cable runs.

Therefore, keep cable runs as short as possible.

6. Switching of inductive loads produces high EMI. Use of snubbers across

inductive loads suppresses EMI.
Snubbers:

RLC #SNUB0000

WIRING CONNECTIONS

The bottom board has a removable terminal block where the solid state

outputs and the power connections are made. The top board has a removable
terminal block where the signal inputs, user inputs, and serial communications
connections are made. When wiring the unit, remove the terminal block and use
the numbers on the top label to identify the position number with the proper
function. All conductors should meet voltage and current ratings for each
terminal. Also cabling should conform to appropriate standards of good
installation, local codes and regulations. It is recommended that power
supplied to the unit (AC or DC) be protected by a fuse or circuit breaker.

Strip the wire, leaving approximately 1/4" bare wire exposed (stranded

wires should be tinned with solder). Insert the wire into the terminal and tighten
down the screw until the wire is clamped in tightly. Each terminal can accept up
to two 18 gauge wires. After the terminal block is wired, install it in the proper
location at the rear of the unit. Wire each terminal block in this manner.

-40-

Advertising