Appendix A. CRBasic Program for Version 18

A-6

'Measure PRT and convert to C and Deg F.

'The PRT was originally included so that we could perform temperature corrections on

'the load cell. However, after several cycles in the temperature chamber, it was found

'that a temperature correction was not necessicary. We left the PRT on the sensor

'so anyone who wanted to could verify our findings.

BrHalf3W

(PRT_raw,1,mV250C,13,Vx2,2,2500,True,0,250,10,0)

PRT

(PRT_C,1,PRT_raw,1.0,0)

PRT_F=((PRT_C)*1.8)+32

If TimeIntoInterval (0,15,Min) AND RecordAccumulation Then

If Accum_15m.PrecipF_in(1,1) <> NAN Then

FifteenMinAccum

=

PrecipF_in

-

Accum_15m.PrecipF_in(1,1)

Else

FifteenMinAccum = PrecipF_in '- 0 ''subtracting zero

EndIf

If FifteenMinAccum < 0.002 Then 'Register only if the difference is more than 0.002"

'the assumption here is that the load cell will drift less than the accumulation.

FifteenMinAccum=0
EndIf

TotFAccum = TotFAccum + FifteenMinAccum

TotAccum

=

Round

(TotFAccum,2)


CallTable

(Accum_15m)


EndIf

'Call Data Tables to output data.

CallTable

(Rain_15m)

CallTable

(Rain_1h)

CallTable

(Rain_1d)


If PrecipF_in <0.002 Then PrecipF_in = 0

If Precip_in<0.002 Then Precip_in = 0


NextScan

SlowSequence
Scan

(1,Sec,3,0)

Time

=

Status.TimeStamp(1,1)

StaName

=

Status.StationName

OSVer

=

Status.OSVersion

ProgName

=

Status.ProgName

StartTime

=

Status.StartTime(1,1)

NextScan

EndProg