Safety

UL for US approved according to UL195O Std.

C-UL(UL for Canada) approved according to C22.2 No.950 Std.

CE for Europe approved according to EN 60950 Std.

Laser components are Laser Class I approved:
— EN-60825/IEC-825 for Europe
— FDA CFR 1040 for USA

Safety - AC Version

Overcurrent Protection: A readily accessible Listed safety-approved protective
device with a 16A rating must be incorporated in series with building
installation AC power wiring for the equipment under protection.

Safety - DC Version

Restricted Access Area: This unit must be installed in Restricted Access Areas
only.

Installation Codes: This unit must be installed in accordance with the US
National Electrical Code, Article 110 and the Canadian Electrical Code, Section
12.

Conductor Ampacity: Per UL 1950, Annex NAE (NEC Article 645-5(a)), the
branch-circuit conductors supply shall have the ampacity of not less than 125
percent of the total connected load. For input leads use at least 18 AWG copper
conductors.

Overcurrent Protection: Per UL 1950, Annex NAE (NEC Article 240-3), a readily
accessible listed branch-circuit overcurrent protective device rated maximum
10A must be incorporated into the building wiring.

EMC Emissions

Emissions

Approved according to:

US - FCC Part 15 sub part B, class A

Europe - EN55022 class A and EN61000-3-2

Japan - VCCI-A

Immunity

Approved according to:

EN 55024 and EN61000-3-3