3.7. Guidelines for mounting (IP55/IP66 Units)
•
Before mounting the drive, ensure that the chosen location meets the environmental condition requirements for the drive shown in
section 10.1
•
The drive must be mounted vertically, on a suitable flat surface
•
The minimum mounting clearances as shown in the table below must be observed
•
The mounting site and chosen mountings should be sufficient to support the weight of the drives
Drive
Size
X
Above & Below
Y
Either Side
mm
mm
2 (IP66)
200
10
3 (IP66)
200
10
4 (IP55)
200
10
5 (IP55)
200
10
6 (IP55)
200
10
7 (IP55)
200
10
Note :
Typical drive heat losses are 3% of operating load
conditions.
Above are guidelines only and the operating ambient
temperature of the drive MUST be maintained at all
times.
Cable Gland Sizes
Drive
size
Power
Cable
Motor
Cable
Control
Cables
2
M25 (PG21)
M25 (PG21)
M20 (PG13.5)
3
M25 (PG21)
M25 (PG21)
M20 (PG13.5)
4
M32 (PG29)
M32 (PG29)
M20 (PG13.5)
5
M50 (PG36)
M50 (PG36)
M20 (PG13.5)
6 and 7
No predrilled glandholes
•
Using the drive as a template, or the dimensions shown above, mark the locations required for drilling
•
Suitable cable glands to maintain the IP protection of the drive are required. Gland sizes should be selected based on the number and
size of the required connection cables. Drives are supplied with either predrilled holes or a plain, undrilled gland plate to allow the
correct hole sizes to be cut as required. Remove the gland plate from the drive prior to drilling.
X
X
Y
Y