9.2.2. Modbus Control & Monitoring Registers 

The following is a list of accessible Modbus Registers available in the Drive.  

•

When Modbus RTU is configured as the Fieldbus option, all of the listed registers can be accessed.  

•

Registers 1 and 2 can be used to control the drive providing that Modbus RTU is selected as the primary command source (P1‐12 = 4) 
and no Fieldbus Option Module is installed in the drive Option Slot. 

•

Register 3 can be used to control the output torque level providing that  

o

The drive is operating in Vector Speed or Vector Torque motor control modes (P4‐01 = 1 or 2) 

o

The torque controller reference / limit is set for ‘Fieldbus’ (P4‐06 = 3) 

•

Register 4 can be used to control the acceleration and deceleration rate of the drive providing that Fieldbus Ramp Control is enabled 
(P5‐07 = 1) 

•

Registers 6 to 24 can be read regardless of the setting of P1‐12 

Register 
Number 

Upper Byte 

Lower Byte 

Read 

Write 

Notes 

1

 

Command Control Word 

R/W 

Command control word used to control the Drive when operating with Modbus RTU. 
The Control Word bit functions are as follows :‐ 
Bit 0 : Run/Stop command. Set to 1 to enable the drive. Set to 0 to stop the drive. 
Bit 1 : Fast stop request. Set to 1 to enable drive to stop with 2

nd

 deceleration ramp. 

Bit 2 : Reset request. Set to 1 in order to reset any active faults or trips on the drive.  
This bit must be reset to zero once the fault has been cleared. 
Bit 3 : Coast stop request. Set to 1 to issue a coast stop command. 

2

 

Command Speed Reference 

R/W 

Setpoint must be sent to the drive in Hz to one decimal place, e.g. 500 = 50.0Hz 

3

 

Command Torque Reference 

R/W 

Setpoint must be sent to the drive in % to one decimal place, e.g. 2000 = 200.0% 

4

 

Command Ramp times 

R/W 

This register specifies the drive acceleration and deceleration ramp times used when 
Fieldbus Ramp Control is selected (P5‐08 = 1) irrespective of the setting of P1‐12. The 
input data range is from 0 to 60000 (0.00s to 600.00s) 

6

 

Error code

 

Drive status

R 

This register contains 2 bytes.  
The Lower Byte contains an 8 bit drive status word as follows :‐ 
Bit 0 : 0 = Drive Disabled (Stopped), 1 = Drive Enabled (Running)  
Bit 1 : 0 = Drive Healthy, 1 =  Drive Tripped 
The Upper Byte will contain the relevant fault number in the event of a drive trip. 
Refer to section Error! Reference source not found. for a list of fault codes and 
diagnostic information 

7

 

Output Frequency 

R 

Output frequency of the drive to one decimal place, e.g.123 = 12.3 Hz 

8

 

Output Current 

R 

Output current of the drive to one decimal place, e.g.105 = 10.5 Amps 

9

 

Output Torque 

R 

Motor output torque level to one decimal place, e.g. 474 = 47.4% 

10

 

OutputPower 

R 

Output power of the drive to two decimal places, e.g.1100 = 11.00 kW 

11

 

Digital Input Status 

R 

Represents the status of the drive inputs where Bit 0 = Digital Input 1 etc. 

20

 

Analog 1 Level 

R 

Analog Input 1 Applied Signal level in % to one decimal place, e.g. 1000 = 100.0% 

21

 

Analog 2 Level 

R 

Analog Input 2 Applied Signal level in % to one decimal place, e.g. 1000 = 100.0% 

22

 

Pre Ramp Speed Reference 

R 

Internal drive frequency setpoint 

23

 

DC bus voltages 

R 

Measured DC Bus Voltage in Volts 

24

 

Drive temperature 

R 

Measured Heatsink Temperature in °C 

9.2.3. Modbus Parameter Access 

All User Adjustable parameters (Groups 1 to 5) are accessible by Modbus, except those that would directly affect the Modbus communications, 
e.g. 

•

P5‐01 Communication Protocol Select 

•

P5‐02 Drive Fieldbus Address 

•

P5‐03 Modbus RTU Baud Rate 

•

P5‐04 Modbus RTU Data Format 

All parameter values can be read from the drive and written to, depending on the operating mode of the drive – some parameters cannot be 
changed whilst the drive is enabled for example. 
 
When accessing a drive parameter via Modbus, the Register number for the parameter is the same as the parameter number,  
E.g. Parameter P1‐01 = Modbus Register 101. 
Modbus RTU supports sixteen bit integer values, hence where a decimal point is used in the drive parameter, the register value will be multiplied 
by a factor of ten, 
E.g. Read Value of P1‐01 = 500, therefore this is 50.0Hz. 
 
For further details on communicating with Drive using Modbus RTU, please refer to your local distributor or Sales Partner. 