3.8. Guidelines for mounting (IP40 Units) 

Before mounting the drive, ensure that the chosen location meets the environmental condition requirements for the drive shown in section 
10.1 

The drive must be floor standing, placed on a Horizontal and suitably flat surface 

The Enclosure must be anchored to an adjacent wall using the mounting points provided 

All Enclosure vents must remain clear with airflow unobstructed 

The mounting site and chosen mountings should be sufficient to support the weight of the drives 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note : 

 
Typical drive heat losses are 3% of operating load 
conditions. 
 
Above are guidelines only and the operating ambient 
temperature of the drive MUST be maintained at all 
times. 

3.9. Removing the Terminal Cover 

3.9.1. Frame Sizes 2& 3 

 

 

Using a suitable flat blade screwdriver, rotate the two retaining 
screws indicated until the screw slot is vertical. 

Level Ground 