4.8. Control Terminal Wiring 

•

All analog signal cables should be suitably shielded. Twisted pair cables are recommended. 

•

Power and Control Signal cables should be routed separately where possible, and must not be routed parallel to each other 

•

Signal levels of different voltages e.g. 24 Volt DC and 110 Volt AC, should not be routed in the same cable.

 

•

Maximum control terminal tightening torque is 0.5Nm

 

4.9. Connection Diagram 

4.9.1. Power Terminal Designations 

Incoming Mains Power Supply 
For 1 Phase Supply, connect to 
L1/L and L2/N terminals. 
For 3 Phase Supply, connect to 
L1, L2 & L3 terminals. 
Phase sequence is not 
important. 

 

Motor Connections
Connect the motor to the U, V & W 
terminals. 
The motor earth must be connected 
to the drive 
Optional Brake Resistor & DC Bus 
Connections 
Where a Brake resistor is used, it 
must be connected to the BR+ and 
DC+ terminals 

Protective Earth / Ground 
connection. 
The drive must be Earthed / 
Grounded 

4.9.2. Control Terminal Connections& Factory Settings 

 

Open 

Closed 

 

 

+24V Supply (100mA) / External Input 

+24V 

1 

 

 

 

Digital Input 1 

Stop  

Run (Enable) 

DIN1 

2 

 

Digital Input 2 

Forward Rotation 

Reverse Rotation 

DIN2 

3 

 

Digital Input 3 

Analog Speed Ref 

Preset Speed 

DIN3 

4 

 

Digital Inputs : 8 – 30 Volt DC 
+ 10 Volt, 10mA Output 

+10V 

5 

 

Analog Input 1 (Digital input 4) 

AIN1 

6 

 

 

0V 

7 

0V 

 

Output Speed 

Analog Output : 0 – 10 Volt / 4‐20mA, 20mA Max 

 

8 

AOUT1 

0 Volt Supply / External Input 

0V 

9 

0V 

 

Output Current 

Analog Input 2 (Digital input 5) 

AIN2 

10 

 

Analog Output : 0 – 10 Volt / 4‐20mA, 20mA Max 

 

11 

AOUT2 

External Hardware Enable Cicuit 

STO+ 

12 

 

 

 

STO‐ 

13 

 

Relay Contacts 
250VAC / 30VDC 
5A Maximum 

 

14 

RL1‐C 

 

Default Function :  
Healthy 
/ Fault 

 

15 

RL1‐NO 

 

16 

RL1‐NC 

 

17 

RL2‐A 

 

Default Function :  
Running 

 

18 

RL2‐B 

 

L1 / L

L2 / N

L3