Serial communication settings, Fnio s-series – Beijer Electronics NA-9379 User Manual

Page 32

Advertising
background image

32

MODBUS Programmable I/O NA-9379

FnIO S-Series



Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr

5.5. Serial Communication Settings


Setting according to the each communication state is possible Because NA-9379 is available the
RS232 and RS485 Serial Communications.

Station Setting
The following illustration is an area of Register 0x160A address that can be used to set the code of Serial
communication. High 1byte is the area of rs232, and Low 1byte is the area of rs485.
It is possible to set a maximum of 247 for each area. (default : 1)

MSB LSB

0x160A

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0


RS232C Modbus station RS485 Modbus station

RS232/ RS485 Communication setting

The options for the communication can be selected.
RS232 can be selected from the register address, “0x1606”.
RS485 can be selected from the register address, “0x1608”.

- 1 nibble : Data bit(0 : 8bit(default), 1 : 9bit)
- 2 nibble : Stop bit(0 : 1bit(default), 1 : 2bit)
- 3 nibble : Parity bit(0 : none(default), 1: even, 2 : odd)
- 4 nibble : Reserve

MSB LSB

0x1607

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Data bit Stop bit Parity bit Reserve

RS232

MSB LSB

0x1609

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Data bit Stop bit Parity bit Reserve

RS485

Baudrate setting
The baudrate from 1200bps to 115200bps is supported.
RS232 can be selected from the register address, “0x1606”.
RS485 can be selected from the register address, “0x1608”.

1 : 2400 2 : 4800 3 : 9600 4 : 19200
5 : 38400 (default) 6 : 57600 7 : 115200