A.3.4. 4 (0x04) Read Input Registers
This function code is used to read from 1 to approx. 125 contiguous input registers in a remote device. The
Request PDU specifies the starting register address and the number of registers. The register data in the response
message are packed as two bytes per register, with the binary contents right justified within each byte. For each
register, the first byte contains the high order bits and the second contains the low order bits.

Request

Field name

Example

RTU

ASCII

ASCII (bus line)

Start of Frame

-

t1-t2-t3

“,”

0x3A

Slave Address

0x07

0x07

“07”

0x30, 0x37

Function Code

0x04

0x04

“04”

0x30, 0x34

Starting Address Hi

0x00

0x00

“00”

0x30, 0x30

Starting Address Lo

0x00

0x00

“00”

0x30, 0x30

Quantity of Register Hi

0x00

0x00

“00”

0x30, 0x30

Quantity of Register Lo

0x02

0x02

“02”

0x30, 0x32

Error Check (CRC/LRC)

-

0x71, 0xAD

“F3”

0x46, 0x33

End of Frame

-

t1-t2-t3

CR, LF

0x0D, 0xA

Response

Field name

Example

RTU

ASCII

ASCII (bus line)

Start of Frame

-

t1-t2-t3

“,”

0x3A

Slave Address

0x07

0x07

“07”

0x30, 0x37

Function Code

0x04

0x04

“04”

0x30, 0x34

Byte Count

0x04

0x04

“04”

0x30, 0x34

Input Register #0 Hi

0x00

0x00

“00”

0x30, 0x30

Input Register #0 Lo

0x80

0x80

“80”

0x38, 0x30

Input Register #1 Hi

0x00

0x00

“00”

0x30, 0x30

Input Register #1 Lo

0x00

0x00

“00”

0x30, 0x30

Error Check (CRC/LRC)

-

0x9C, 0x6C

“71”

0x37, 0x31

End of Frame

-

t1-t2-t3

CR, LF

0x0D, 0xA

-

In case of address 0x0000, 0x0001 input register value: 0x0080, 0x0000.