A.3.2. 2 (0x02) Read Discrete Inputs
This function code is used to read from 1 to 2000 contiguous status of discrete inputs in a remote device. The
Request PDU specifies the starting address, i.e. the address of the first input specified, and the number of inputs. In
the PDU Discrete Inputs are addressed starting at zero. Therefore Discrete inputs numbered 1-16 are addressed as
0-15. The discrete inputs in the response message are packed as one input per bit of the data field.
Status is indicated as 1= ON; 0= OFF.

Request

Field name

Example

RTU

ASCII

ASCII (bus line)

Start of Frame

-

t1-t2-t3

“,”

0x3A

Slave Address

0x07

0x07

“07”

0x30, 0x37

Function Code

0x02

0x02

“02”

0x30, 0x32

Starting Address Hi

0x00

0x00

“00”

0x30, 0x30

Starting Address Lo

0x00

0x00

“00”

0x30, 0x30

Quantity of Inputs Hi

0x00

0x00

“00”

0x30, 0x30

Quantity of Inputs Lo

0x0A

0x0A

“0A”

0x30, 0x41

Error Check (CRC/LRC)

-

0xF8, 0x6B

“ED”

0x45, 0x44

End of Frame

-

t1-t2-t3

CR, LF

0x0D, 0xA

Response

Field name

Example

RTU

ASCII

ASCII (bus line)

Start of Frame

-

t1-t2-t3

“,”

0x3A

Slave Address

0x07

0x07

“07”

0x30, 0x37

Function Code

0x02

0x02

“02”

0x30, 0x32

Byte Count

0x02

0x02

“02”

0x30, 0x32

Input Status

0x80

0x80

“80”

0x38, 0x30

Input Status

0x00

0x00

“00”

0x30, 0x30

Error Check (CRC/LRC)

-

0x50, 0x78

“75”

0x37, 0x35

End of Frame

-

t1-t2-t3

CR, LF

0x0D, 0xA

-

In case of address 0x0015~0x0000 output bit value: 00000000_10000000.