A.4.3. Adapter Watchdog Time, other Time Special Register (0x1020, 4128)

A watchdog timer can be configured for timeout periods up to 65535(1unit=100msec). The Watchdog timer will
timeout (timer decreased, reached 0) if MODBUS operation to the slave node does not occur over the configured
watchdog value, then the slave adapter forces that slot output value is automatically set to user-configured fault
actions and values.

Address

Access

Type, Size

Description

0x1020(4128)

Read/Write 1 word

Watchdog time value 16bit unsigned.
The time value is represented by multiples of 100msec.
The 0 (watchdog timeout disabled) is default value.
A changing of watchdog time value resets watchdog error and
counter.

0x1021(4129)

Read

1 word

Watchdog timer remain value
This value is decreased every 100msec

0x1022(4130)

Read

1 word

Watchdog error counter, it is cleared by writing address
0x1020

0x1023(4131)

Read/Write 1 word

Enable/disable auto recovery Watchdog error when receiving
new frame.
0:Disable, 1:Enable(default). Its value is stored in EEPROM.

0x1028(4136)

Read

4 words

I/O update time, Expansion Module Process time, CoDeSys
update time, CoDeSys Process Time. (1usec unit)