A.3.3. 3 (0x03) Read Holding Registers
This function code is used to read the contents of a contiguous block of holding registers in a remote device. The
Request PDU specifies the starting register address and the number of registers.
The register data in the response message are packed as two bytes per register, with the binary contents right
justified within each byte. For each register, the first byte contains the high order bits and the second contains the
low order bits.

Request

Field name

Example

RTU

ASCII

ASCII (bus line)

Start of Frame

-

t1-t2-t3

“,”

0x3A

Slave Address

0x07

0x07

“07”

0x30, 0x37

Function Code

0x03

0x03

“03”

0x30, 0x33

Starting Address Hi

0x08

0x08

“08”

0x30, 0x38

Starting Address Lo

0x00

0x00

“00”

0x30, 0x30

Quantity of Register Hi

0x00

0x00

“00”

0x30, 0x30

Quantity of Register Lo

0x02

0x02

“02”

0x30, 0x32

Error Check (CRC/LRC)

-

0xC6, 0x0D

“EC”

0x45, 0x43

End of Frame

-

t1-t2-t3

CR, LF

0x0D, 0xA

Response

Field name

Example

RTU

ASCII

ASCII (bus line)

Start of Frame

-

t1-t2-t3

“,”

0x3A

Slave Address

0x07

0x07

“07”

0x30, 0x37

Function Code

0x03

0x03

“03”

0x30, 0x33

Byte Count

0x04

0x04

“04”

0x30, 0x34

Output Register #0 Hi

0x11

0x11

“11”

0x31, 0x31

Output Register #0 Lo

0x22

0x22

“22”

0x32, 0x32

Output Register #1 Hi

0x33

0x33

“33”

0x33, 0x33

Output Register #1 Lo

0x44

0x44

“44”

0x34, 0x34

Error Check (CRC/LRC)

-

0x2D, 0xC6

“38”

0x33, 0x38

End of Frame

-

t1-t2-t3

CR, LF

0x0D, 0xA

-

In case of address 0x0800, 0x0801 output register value: 0x1122, 0x3344.