A.4.5. Adapter Setting Special Register (0x1600, 5632)

Address

Access

Type, Size

Description

0x1600(5632)

Read

2word

IP Address. (ex : C0A8 6464 = 192.168.100.100)

0x1602(5634)

Read

2word

Subnet Mask. (ex : FFFF FF00 = 255.255.255.0)

0x1604(5636)

Read

2word

Gate way. (ex : C0A8 0001 = 192.168.0.1)

0x1606(5638)

Read/Write 1word

RS-232 Baudrate. (1200bps~115200bps)
1 : 2400 2 : 4800 3 : 9600 4 : 19200
5 : 38400 (default) 6 : 57600 7 : 115200

0x1607(5639)

Read/Write 1word

RS-232 Setting.
- 1 nibble : Data bit(0 : 8bit(default), 1 : 9bit)
- 2 nibble : Stop bit(0 : 1bit(default), 1 : 2bit)
- 3 nibble : Parity bit(0 : none(default), 1: even, 2 : odd)
- 4 nibble : Reserve

0x1608(5640)

Read/Write 1word

RS-485 Baudrate. (1200bps~115200bps)
1 : 2400 2 : 4800 3 : 9600 4 : 19200
5 : 38400 (default) 6 : 57600 7 : 115200

0x1609(5641)

Read/Write 1word

RS-485 Setting.
- 1 nibble : Data bit(0 : 8bit(default), 1 : 9bit)
- 2 nibble : Stop bit(0 : 1bit(default), 1 : 2bit)
- 3 nibble : Parity bit(0 : none(default), 1: even, 2 : odd)
- 4 nibble : Reserve

0x160A(5642)

Read/Write 1word

MODBUS Station.
- High 1byte : Station No. of RS-232C (default : 1)
- Low 1byte : Station No. of RS-485 (default : 1)

0x160B(5643)

Read/Write 1word

IP Setting Method.
- Not Use : 0x0000 - BootP : 0x8000 (default)
- DHCP : 0x8001

0x1610(5648)

Read

3word

Mac Address (ex : 0014 F700 0101 = 00.14.F7.00.01.01)

0x1620(5664)

Read/Write 4word

RTC
- 1 word : 00ss (ss : sec)
- 2 word : hhmm (hh : hour, mm : min)
- 3 word : mmdd (mm : month, dd : day)
- 4 word : yyyy (yyyy : year)
(ex : 07D8 0514 0F19 0006 = 2008. 05.20. 15.25. 06)