Auxiliary digital input and key, Feeder, Manual operation mode – NOVUS N1500FT Indicator User Manual

Page 3: 24 vdc auxiliary power supply, Installation, Installation recommendations, Electrical connections, Power supply connection, Connections for input and output signals

Advertising
background image

N1500FT Flow Indicator

NOVUS AUTOMATION

3/9

AUXILIARY DIGITAL INPUT AND

KEY

Similarly to a digital input, the

key can be set to zero the

totalizer, freeze the main screen, zero minimum and maximum

readings or control the feeder function.

FEEDER
The feeder function is used to control the volume of fluids based on

its flow rate. It is typically used for storage applications, where there

is a start signal that triggers a relay and the flow rate begins to be

measured. When reaching a given setpoint, this relay is deactivated

to stop flow.
Its use depends on correct configuration of the related alarm.
During the feeder process, it is not possible to change the alarm

setpoint. Process should be reset first to allow it.
Functions of

key and/or digital input, when assigned to the

feeder function:

• When the

key or digital input is activated, the feeder

process is started, activating all relays related to the feeder alarm;

• In case the

key or digital input is activated once again, the

process is frozen and all relays related to the feeder alarm are

deactivated;

• To restart the feeder process,

key or digital input must be

activated for 3 seconds, until the process is restarted, zeroing all

existing feeder indication. This can be done with the process

stopped or running;

• At the end of the feeder process, when alarm setpont is reached,

process values are frozen and all related relays are deactivated.
To restart a new process, just activate the

key or digital

input for all counters to be reset and process will start running;

In case of a power shortage, if the feeder batch reset parameter
(

Bat.rst

) is configured as

no

, whenever the equipment

powers up again the process will restore from where it stopped.

This means that, if it was in the middle of a feeder process, all

relays assigned to the feeder alarm will be activated. If the

process was stopped, all counters will keep their values and the

process will remain stopped until it is activated either by the

key or the digital input.

MANUAL OPERATION MODE
In the hardware cycle, outputs can be set manually. This can be

extremely useful for tests and simulations. After exiting the cycle,

outputs go back to their regular status.

24 VDC AUXILIARY POWER SUPPLY
DC power supply models provide a 24 Vdc output for field transmitters.

INSTALLATION

The indicator must be installed on a panel. To do so, remove the two

plastic clamps, introduce the device in the panel cutout and put the

clamps back from the rear side of the indicator.

INSTALLATION RECOMMENDATIONS
• Input signal conducers should be disposed in the system

separately from output conducers and power conducers,

preferably in grounded electrodes.

• Instruments should be powered through a dedicated network.
• For control and monitoring applications it is vital to consider what

might happen if any part of the system fails. The alarm internal

relay does not ensure total protection.

• It is recommended to use RC FILTERS (47 Ω and 100 nF, series)

in contactor coils, solenoid coils, etc.

ELECTRICAL CONNECTIONS
All the inside can be removed without the need to undo the electrical

connections. Disposition of signals in the rear panel of the indicator is

shown in Fig. 1.

Fig. 1 – Rear panel connections

POWER SUPPLY CONNECTION

Fig. 2 – Power supply terninals

CONNECTIONS FOR INPUT AND OUTPUT SIGNALS
It is important that these connections are well made, with signal or

sensor wires securely attached to rear panel terminals. Check the

“Specifications” section for the range of the input signals.

The images below show connections for different input types:

Fig. 3 – Auxiliary digital input

connection

Fig. 4 - Flow pulse input –

Voltage signals

Fig. 5 -

Flow pulse input –

NPN signals

Fig. 6 - Flow pulse input –

PNP signals

Fig. 7 - Flow pulse input – Dry

contact signals

Fig. 8 – Coil Signal connection

(magnetic pickup)

Advertising