Specifications, Warranty – NOVUS N1500FT Indicator User Manual

Page 9

Advertising
background image

N1500FT Flow Indicator

NOVUS AUTOMATION

9/9

SPECIFICATIONS

DIMESIONS: ............................................ 48 x 96 x 92 mm (1/16 DIN)

............................................................ Approximate Weight: 242 g

PANEL CUTOUT: .................................. 45.5 x 93 mm (+0.5 -0.0 mm)
POWER SUPPLY: ..................... 100 to 240 Vac/dc (±10 %), 50/60 Hz

Optionally: .......................................................... 24 Vdc/ac ±10 %

Maximum Consumption: .................................................... 7.5 VA

ENVIRONMENTAL CONDITIONS:

Operation Temperature: ............................................... 5 to 50 °C

Relative Humidity: ...................................... 80 % max. up to 30 ºC

For temperatures above 30 °C, reduce 3% by °C

Internal use; Category of installation II, Degree of pollution 2;

altitude < 2000 m

INPUTS

4-20 mA: ......................................... Accuracy: ± 0.2% of full scale

Dry Contact: ........................................... Frequency: 0.1 to 10 Hz

Pulse (Tension, NPN or PNP): ........ Frequency: 0.1 to 50000 Hz

........................................................... Amplitude: from 4 V to 24 V

........................................................ Accuracy: ± 30 ppm @ 25 °C

Magnetic Pickup: ........... Frequency: 0.1 to 8000 Hz @ 30 mVpp

........................................................ 0.1 to 50000 Hz @ 250 mVpp

................................................ Amplitude: from 30 mVpp to 5 Vpp

........................................................... Accuracy: ± 0.1 % @ 25 °C

Input impedance: .....................4-20 mA: 150

Ω (+4.5 Vdc @ 20 mA)

OUTPUTS:

4-20 mA: .............................................. 550 Ω max., 10000 levels

........................................................................ Isolation: 250 Vrms

Pulse: .............................................. Maximum frequency: 100 Hz

....................................................................... Voltage: 0 to 30 Vdc

............................................................... Maximum current: 15 mA

........................................................................ Isolation: 250 Vrms

OUTPUT RELAYS:

ALM1 and ALM2: ..........................................................................

................................ SPDT: 3 A / 240 Vac (3 A / 30 Vdc resisitive)

ALM3 and ALM4: ..........................................................................

....................... SPST-NA: 1.5 A / 250 Vac (3 A / 30 Vdc resisitive)

ELECTROMAGNETIC COMPATIBILITY: ...........................................

........................................ EN 61326-1:1997 and EN 61326-1/A1:1998
SAFETY: .......................... EN61010-1:1993 and EN61010-1/A2:1995

Connections suitable for fork-type terminals 6.3 mm.

PROTECTION: ................................................................................. IP65

FRONT PANEL: ............................................. UL94 V-2 polycarbonate

HOUSING: ................................................................ ABS+PC UL94 V-0

Operation is started: three seconds after connection to power

supply.

IDENTIFICATION

N1500FT -

4R -

485 -

24V

A

B

C

D

A: Indicator model:

N1500FT

B: Output relays:

Nothing shown (basic version with two SPDT relays);
4R

(version with two additional SPST relays);

C: Digital Communication:

Nothing shown (basic version with no serial communication);
485

(version with RS485 serial, Modbus protocol)

D: Power Supply:

Nothing shown (basic version, power supply of 100 to 240 Vac);

24V

(version with power supply of 24 Vdc/ac).

WARRANTY

Warranty conditions are available on our web site

www.novusautomation.com

.

Advertising