Input setup cycle, Selection of flow input type, Output setup cycle – NOVUS N1500FT Indicator User Manual

Page 6: Relay configuration cycle

Advertising
background image

N1500FT Flow Indicator

NOVUS AUTOMATION

6/9

For screens that show totalizations, whether it is the total or the

non-resettable value, when the reading cannot be shown in six

digits it will be shown in two halves; that is, the lower six digits and

the higher five digits (preceded by a k. to indicate it is the high half)

will be displayed in turns every five seconds.
In case no alarm is configured as “feeder”, a “------“ will be

displayed.
Table 6 shows the options for digital input and the

key.

Off

No function.

Rst.tot

Totalization reset.

kold.1n

Freezes display while the input is active or the

key is pressed.

Rst.MM

Resets minimum and maximum values.

feeder

Start of Feeder function. Further details in the

Feeder

section.

IGnore

Suspends totalization, ignoring input signal,

but keeps retransmission working.

Table 6 - Options for digital input and the

key

INPUT SETUP CYCLE

1N.TYPE

Input Type

Selection of flow input type. See Table 8.

1N.4-20

Input 4 to 20 mA

Selection of 4-20 mA input as auxiliary input.

Available only if flow input is different than 4-20

mA.

1n LL

Input Low Limit

Value for the beginning of the auxiliary input

range. Available only if the 4-20 mA input is

enabled.

1n xL

Input High Limit

Value for the end of the auxiliary input range.

Available only if the 4-20 mA input is enabled.

(Ut0ff

Cut Off

Minimum flow rate for indication. Any flow rate

below this value is shown as 0 and will not

increment the totalizer.

FLTR.1n

Filter Input

4-20 mA input filter. Available only if the 4-20

mA input is enabled.

Un1t 1

Unit

Instantaneous

Unit for indicating instantaneous flow rate. It

also establishes the time base for this

measurement.

Un1t t

Unit totalizer

Unit for totalized flow rate indication.

k.1nst

K Instantaneous

K factor to be applied on the flow rate reading

through the digital input.
Available only if flow input is different than 4-

20 mA.
Instantaneous K factor has its value set as

“pulses per volume”.

k.tot

K totalizer

K factor to be applied on total volume.
When using pulse input, total K factor has its

value set as “pulses per volume”.

S.root

Square root

Square root. Available only if the 4-20 mA

input is enabled. The “YES” option applies

quadratic function on the input signal within

the limits programmed in “inLL” and “inkL”.

Table 7 – Input setup cycle keys

SELECTION OF FLOW INPUT TYPE

SENSOR

DESCRIPTION

4

to

20

4-20 mA analog signal

d.1.nPn

NPN or tension type digital input

D1.PnP

NPN digital input

Sw1tch

Dry Contact (reed switch) digital input

pickvp

Coil signal input (from 30 mVpp)

Table 8 – Input sensor type

Note: For information about reading speed, check Specifications.

OUTPUT SETUP CYCLE

rtll

Retransmition

Low Limit

Retransmission lower limit. It is the flow rate

value that corresponds to the 4-20 mA output

lower limit. When rtkl is equal to rtll,

output is turned off.

rtxl

Retransmition

High Limit

Retransmission higher limit. It is the flow rate

value that corresponds to the 4-20 mA output

higher limit.
When rtll is equal to rtkl, output is

turned off.

0UT.err

Output Error

Value to be applied to 4-20 mA output in case

of input failure.

PULSe

Pulse

Configuration of pulse output. Options are off,

volumetric pulse and frequency.

w.pulse

Volume Pulse

Volume to be accumulated to generate an

output pulse. Available only when pulse output

is set to volumetric pulse.

Pulse.t

Pulse Time

Time period during which pulse remains active

after having reached intended volume.

Available only when pulse output is set to

volumetric pulse.

freqdw

Frequence

Divider

Input frequency divider. Available only when

pulse input is set to frequency.

Table 9 – Output setup cycle keys

When pulse output is set as volumetric pulse, a pulse is generated

every time the totalizer accumulates the value programmed on the
w.pulse screen. For example, if u.pulse is programmed to 10,

then a pulse will be generated for every 10 units of computed

volume.
When pulse output is set to frequency, the output signal will be an

input signal divider.

RELAY CONFIGURATION CYCLE

Rl 1

Relay 1

Relay 1 function selection: off, Al 1, al
2, al 3 e al 4.

Rl 2

Relay 2

Relay 2 function selection: off, Al 1, al
2, al 3 e al 4.

Rl 3

Relay 3

Relay 3 function selection: off, Al 1, al
2, al 3 e al 4.

Rl 4

Relay 4

Relay 4 function selection: off, Al 1, al
2, al 3 e al 4.

Table 10 – Relay configuration cycle screens

If there is need for activating more than one output relay by the same

alarm, just assign the desired relays to the desired alarm. Default

configuration assigns one relay to its related (same index) alarm

(relay 1 for alarm 1, relay 2 for alarm 2, and so on).

Advertising