Configuration / features, Input type selection, Outputs – NOVUS Controller N120 User Manual

Page 2: Digital input, Alarms functions

Advertising
background image

NOVUS AUTOMATION

2/14

The parameters in the operation level have easy access through the

key

P

. The access deeper levels use the combination of keys:

P

and

B

pressed simultaneously

Press P to advance or B to retrocede parameters within a level. At

the end of each level, the controller returns to the operation level.

Keep pressing the P key to move fast forward in the level.
Alternatively, the controller returns to the operation level after

pressing the B key for 3 seconds.
All configuration parameters are stored in protected memory. The

values are saved when the Keys P or B are pressed after changing a

parameter value. The value of SP is saved upon pressing the P key

or every 25 seconds.

CONFIGURATION / FEATURES

INPUT TYPE SELECTION
Select the input type (in parameter “tYPE”) from Table 2 below.

TYPE

CODE

RANGE OF MEASUREMENT

J

Tc j

Range: -110 to 950 ºC (-166 to 1742 ºF)

K

Tc k

Range: -150 to 1370 ºC (-238 to 2498 ºF)

T

Tc t

Range: -160 to 400 ºC (-256 to 752 ºF)

N

Tc n

Range: -270 to 1300 ºC (-454 to 2372 ºF)

R

Tc r

Range: -50 to 1760 ºC (-58 to 3200 ºF)

S

Tc s

Range: -50 to 1760 ºC (-58 to 3200 ºF)

B

Tc b

Range: 400 to 1800 ºC (752 to 3272 ºF)

E

Tc e

Range:-90 to 730 ºC (-130 to 1346 ºF)

Pt100

Pt

Range: -200 to 850 ºC (-328 to 1562 ºF)

0-20 mA

L0.20

Linear Signals

Programmable indication from -1999 to 9999.

4-20 mA

L4.20

0–50 mV

L0.50

0-5 Vdc

L0.5

0-10 Vdc

L0.10

Table 2 - Input types

OUTPUTS
Up to 3 outputs can be configured for control (1 or 2) or alarm. The

available outputs are identified on the rear panel as OvT1, OvT2 e
OvT3. Electrical characteristics of each output are:

OUT1: Voltage Pulse, 5 Vdc / 25 mA;
OUT2 output to Relay SPST-NA;
OUT3 output to Relay SPST-NA;

The option to be used on each output is user-defined according to the

options shown in Table 3 e Table 4.

Outputs Functions

Code

Inoperative

OFF

Alarm 1 output

A1

Alarm 2 output

A2

Alarm 3 output

A3

Alarm 4 output

A4

Loop break detection output

Lbd

Control 1 output

(TR1

Control 2 output

(TR2

Table 3 – Outputs Functions

• In the channel configuration are shown on the display, only the

valid options for each channel. These functions are described

below:

• off - No function.
The I/O channel programmed with code 0 will not be used by the

controller.
• Note: Even though functionless, this channel can be activated by

commands via serial communication (MODBUS command 5).

• a1, a2, a3, a4 - - Alarm output.
Available for all I/O channels. The selected channel can be used as

output to Alarms 1 to 4.
• Lbd – Loop Break Detector function.
Assigns the output of the Loop Break Detector alarm to an I/O

channel. Available to all I/O channels.

(tr1

- Control output 1.

(tr2

- Control output 2.

DIGITAL INPUT
Defines the operation adopted by the available digital input terminals

7 and 8 of the controller. The D.in1 parameter defines the desired

function. There are 5 options possible.

Digital Input Functions

Code

No function

OFF

Automatic/Man mode change

mAN

Run/Stop mode change

RVN

Freezes program execution

K.PRG

Program 1 selection

PR 1

Table 4 – Functions for the digital input channels

• These functions are described below:
• mAn - Digital Input with Auto/Manual function

Closed: Manual control

Opened: Automatic control

• rvn - Digital Input with RUN function

Closed: = outputs enabled

Opened = outputs disabled

• kprg - Digital Input with Hold Program function

Closed: = Enables execution of the program

Opened: = Interrupts (freezes) execution of the program

Note: Even when the execution of the program is interrupted, the

control output remains active and controlling the process at the

point (Setpoint) of interruption. The program will resume its

normal execution starting from this same point when the digital

input is closed.

• Pr 1 - Digital Input with function to Execute Program 1

Defines the IO channel as Digital Input with the function of

commanding the execution of the setpoing profile program 1.

Closed: = Selects program 1

Opened: = Uses main Setpoint

Even with ED in OFF the LogChart can start Logging.

ALARMS FUNCTIONS
The controller has 4 independent alarms. They can be programmed

to operate with eight different functions, represented in Table 5.
• off – Alarms turned off.
• ierr – Sensor break alarm.
It is activated whenever the input sensor is broken or disconnected.
• rs – Ramp & soak program event alarm
This alarm is activated by the Ramp & Soak program (refer to the

programs of ramp and soak section on how to set the event alarm).