Read holding registers – 0x03, Write holding registers – 0x06, Description of some registers – NOVUS AirGate-Modbus User Manual

Page 16: Register 35 – operation channel, Register 36 - link quality indicator rx father, Register 39 - link quality indicator rx child

Advertising
background image

AirGate-Modbus

NOVUS AUTOMATION

16/22

READ HOLDING REGISTERS – 0X03

This command can be used to read the value of one, or up to the maximum amount of consecutive holding registers, as
shown in the “Holding Registers Table.”

WRITE HOLDING REGISTERS – 0X06

This command can be used to write in a holding register, as shown in “Holding Registers Table.”

DESCRIPTION OF SOME REGISTERS

REGISTER 35 – OPERATION CHANNEL

Shows the operation channel that the equipment is operating on the network. It can vary from 11 to 25, where each
channel is equivalent to an operation frequency. Among these 15 possible channels, the network operates on the
channel that has the lowest interference.

CHANNEL

OPERATION FREQUENCY

11

2405 MHz

12

2410 MHz

13

2415 MHz

14

2420 MHz

15

2425 MHz

16

2430 MHz

17

2435 MHz

18

2440 MHz

19

2445 MHz

20

2450 MHz

21

2455 MHz

22

2460 MHz

23

2465 MHz

24

2470 MHz

25

2475 MHz

Table 3 – Operation Channels

REGISTER 36 - LINK QUALITY INDICATOR RX FATHER

States the quality of the reception link of the connection between the equipment and the AirGate-Modbus father with
which it is paired. This value is obtained when measuring the power of the last packet received. This power is measured
in dBm, which is a logarithmic measurement of power in mW. The LQI can vary between -100dBm (worst reception
quality) to -15 dBm (best reception quality).

REGISTER 39 - LINK QUALITY INDICATOR RX CHILD

States the quality of the reception link of the connection between the AirGate-Modbus child whose Modbus address was
filled-out in the ADDR_FILHO register. This value is obtained when measuring the strength of the last packet received.
This power is measured in dBm, which is a logarithmic measurement of power in mW. The LQI can vary between -
100dBm (worst reception quality) to -15 dBm (best reception quality).