34

Used to configure the transmission power of the Wireless interface. The larger the

configured value, the greater the reach.

0 – 0 dBm,
1 – 2 dBm
2 – 4 dBm
3 – 6 dBm
4 – 8 dBm
5 – 10 dBm
6 – 12 dBm
7 – 14 dBm
8 – 20 dBm

R/W

35

Indicates the operation channel which can vary from 11 to 25, According to Anatel

guidelines, the device can operate in the frequencies of channels 11 to 25 for

power levels of up to 20 dBm.

11

25

R

36

LQI RX Father Register
Lists the LQI RX Father, i.e., the quality of the reception link to the network father.

The LQI Rx is a power measurement of the last packet received by the father.

This amount is measured in dBm and varies between -100dBm (worst reception

quality) to -15 dBm (best reception quality). This register has a value of 0 when

the device is in configuration mode or is the network coordinator (that does not

have a father).

-100

-15

R

37

Indicates the number of children (AirGates in operation mode RS485-Slaves +

RHTs-Air) that the device has.

0

43

R

38

ADDR_FILHO register.
This register is used to request the AirGate-Modbus information about its

children.
This register should include the Modbus address of the child that requires the

information contained in the registers 39 to 48.
The information will only be filled out is the Modbus address corresponds to a

device that is in a branch below the one the father belongs to.
If the Modbus address does not belong to a direct child, the information will

correspond to the child en route to the destination.

0

255

R/W

39

LQI RX Child Register.
States the LQI RX Child, i.e., the LQI of the last packet received by the AirGAte of

the child en route to ADDR_FILHO. If ADDR_FILHO is of a child, the LQI

corresponds to it, otherwise, the LQI corresponds to the child of Short Mac

ROTA_FILHO_SHORT_MAC_0 ROTA_FILHO_SHORT_MAC_1.

-100

-15

R

40

States the number of packets requested to the child with the address ADDR_FILHO

as long as AirGate has started until reaching the limit of the register.

0

65535

R

41

States the number of packets answered by the child with the address ADDR_FILHO

as long as AirGate has started until reaching the limit of the register.

0

65535

R

42

Lists the error rate in % * 100.
To obtain the error rate in %, divide the register value by 100.

0

10000

R

43

States the size of the last requested packet to the child with the address

ADDR_FILHO.

0

4096

R

44

States the size of the last requested answered by the child with the address

ADDR_FILHO.

0

4096

R

45

States the throughput of the last transaction that occurred with the slave of address

ADDR_FILHO considering the time from the first byte received by the master’s

request interface until the last byte transmitted from the child’s response to the

master's interface and the size of the request and response packets.
Information available in Bytes/Second.

0

65530

R

46

States the response time of the last transaction that occurred with the slave of

address ADDR_FILHO considering the last byte received by the master’s

requisition interface until the first byte transmitted from the slave’s response

packet to the master’s interface.
Information available in milliseconds.

0

65535

R

47

Register ROTA_FILHO_SHORT_MAC_0.
First Byte of the Short Mac of the AirGate-Modbus route to the child with Modbus

address ADDR_FILHO.

0

255

R

48

Register ROTA_FILHO_SHORT_MAC_1.
First Byte of the Short Mac of the AirGate-Modbus route to the child with Modbus

address ADDR_FILHO.

0

255

R