Ramp and soak profile program, Auto tune – NOVUS Controller N2000 User Manual

Page 7

Advertising
background image

NOVUS AUTOMATION

7/9

RAMP AND SOAK PROFILE PROGRAM

Seven ramp and soak profiles with up to 7 segments each can be
programmed. Longer profiles of up to 49 segments can be created by
linking 2 or more profiles.

SP

tim e

T1

T 2

T3

T 4

T5

SP 0

SP 1

SP 2

SP 3

SP4

SP 5

S P6

SP 7

T6

T 7

Figure 11 - Example of a complete ramp and soak profile

To execute a profile with fewer segments just program 0 (zero) for the
time intervals that follow the last segment to be executed.

SV

time

T1

T2

T3

SP0

SP1

SP2

SP3

T4=0

Figure 12 - Example of a profile with fewer segments. (T4 is set 0)

The program tolerance “Ptol

Ptol

Ptol

Ptol” defines the maximum deviation

between PV and SV for the execution of the profile. If this deviation is
exceeded, the program will be interrupted until the deviation falls to
within the tolerance band.

Programming 0 (zero) at this prompt disables the tolerance and the
profile execution will not to be halted even if PV does not follow SV
(time priority as opposed to SV priority).

The ramp and soak event function is used to activate alarms at any
segment of program 1. This applies only to program 1.

LINK OF PROGRAMS

It is possible to create a more complex program, with up to 49
segments, joining the seven programs. This way, at the end of a
program execution the controller immediately starts to run another one.

When a program is created, it must be defined in the “LP

LP

LP

LP" screen

whether there will be or not another program.

To make the controller run a given program or many programs
continuously, it is only necessary to link a program to itself or the last
program to the first.

SV

time

T1

T2

T3

T4

T5

T1

T2

T3

T4

SP0

SP1

SP2

SP3

SP4

SP5 / SP0

SP1 SP2

SP3

SP4

Program 1

Program 2

Fig. 13 - Example of two linked programs

EVENT ALARM

To enable this event function the alarms to be activated must be
selected for rS

rS

rS

rS function and are programmed at the PE

PE

PE

PE 0

0

0

0 to PE

PE

PE

PE 5

5

5

5

prompts. The number to be programmed at the prompt defines the
alarms to be activated (Table 5).

CODE

ALARM 1

ALARM 2

ALARM 3

ALARM 4

0

0

0

0

1

1

1

1

X

2

2

2

2

X

3

3

3

3

X

X

4

4

4

4

X

5

5

5

5

X

X

6

6

6

6

X

X

7

7

7

7

X

X

X

8

8

8

8

X

9

9

9

9

X

X

10

10

10

10

X

X

11

11

11

11

X

X

X

12

12

12

12

X

X

13

13

13

13

X

X

X

14

14

14

14

X

X

X

15

15

15

15

X

X

X

X

Table 5 - Event codes for ramp and soak

To configure and execute a ramp and soak program:

Program the tolerance value, SV, time and event.

If any event alarm is required program the ramp and soak event

function.

Set the control mode to automatic.

Select ramp and soak program to be executed at prompt Prn

Prn

Prn

Prn

(0 to 7)

Start control at the rvn

rvn

rvn

rvn prompt by selecting YES.

Before executing the program the controller waits for PV to reach the
first set point SP0

SP0

SP0

SP0 if PtoL

PtoL

PtoL

PtoL is different than zero.

Should any power failure occur the controller resumes at the
beginning of the segment it currently is.

AUTO TUNE

During auto tune the process is controlled in ON/OFF mode at the
programmed SetPoint (SV). Depending on the process
characteristics large oscillations above and below SV may occur and
auto tuning may take several minutes to be concluded.

The recommended procedure is as follows:

Disable the control output at the rvn

rvn

rvn

rvn prompt by selecting NO.

Select auto mode operation at the Avto

Avto

Avto

Avto prompt by selecting YES.

Disable the ramp and soak function (select NO) and program a new

SV value other than the present PV (close to the desired set point).

Enable auto tuning at the Atvn

Atvn

Atvn

Atvn prompt by selecting YES.

Enable the control output at the rvn

rvn

rvn

rvn prompt by selecting YES.

During the auto tune procedure the soft-start function will not operate
and large oscillations will be induced around the setpoint. Make sure the
process can accept these oscillations and fast control output changes.

If auto tuning results are not satisfactory refer to Table 6 for manual
fine tuning procedure.

PARAMETER

RESPONSE

SOLUTION

Slow Response

Decrease

Proportional Band

Large Oscillation

Increase

Slow Response

Incre ase

Integral Rate

Large Oscillation

Decrease

Slow Response or Instability

Decrease

Derivative Time

Large Oscillation

Increase

Table 6 - Suggestions for manual tuning of PID parameters

Advertising