CXM Controls:

For detailed control information, see the CXM Application,

Operation and Maintenance manual.

Field Selectable Inputs

Test mode: Test mode allows the service technician to check

the operation of the control in a timely manner. By momen-

tarily shorting the test terminals, the CXM control enters a

20 minute test mode period in which all time delays are sped

up 15 times. Upon entering test mode, the status LED will

flash a code representing the last fault. For diagnostic ease

at the thermostat, the alarm relay will also cycle during test

mode. The alarm relay will cycle on and off similar to the

status LED to indicate a code representing the last fault, at

the thermostat. Test mode can be exited by shorting the test

terminals for 3 seconds.
Retry Mode: If the control is attempting a retry of a fault, the

status LED will slow flash (slow flash = one flash every 2

seconds) to indicate the control is in the process of retrying.

Field Configuration Options

Note: In the following field configuration options, jumper

wires should be clipped ONLY when power is removed from

the CXM control.
Water coil low temperature limit setting: Jumper 3 (JW3-

FP1 Low Temp) provides field selection of temperature limit

setting for FP1 of 30°F or 10°F [-1°F or -12°C] (refrigerant

temperature).
Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].
Air coil low temperature limit setting: Jumper 2 (JW2-FP2

Low Temp) provides field selection of temperature limit set-

ting for FP2 of 30°F or 10°F [-1°F or -12°C] (refrigerant tem-

perature). Note: This jumper should only be clipped under

extenuating circumstances, as recommended by the factory.
Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C].
Alarm relay setting: Jumper 1 (JW1-AL2 Dry) provides field

selection of the alarm relay terminal AL2 to be jumpered to

24VAC or to be a dry contact (no connection).
Not Clipped = AL2 connected to R. Clipped = AL2 dry con-

tact (no connection).

DIP Switches

Note: In the following field configuration options, DIP

switches should only be changed when power is removed

from the CXM control.
DIP switch 1: Unit Performance Sentinel Disable - provides

field selection to disable the UPS feature.
On = Enabled. Off = Disabled.
DIP switch 2: Stage 2 Selection - provides selection of

whether compressor has an “on” delay. If set to stage 2, the

compressor will have a 3 second delay before energizing.

Also, if set for stage 2, the alarm relay will NOT cycle during

test mode.
On = Stage 1. Off = Stage 2
DIP switch 3: Not Used.

DIP switch 4: If Set to “EH2 normal,” EH2 will operate as

standard electric heat output.
On = EH2 Normal.
NOTE: Some CXM controls only have a 2 position DIP

switch package. If this is the case, this option can be se-

lected by clipping the jumper which is in position 4

of SW1.
Jumper not clipped = EH2 Normal.
DIP switch 5: Factory Setting - Normal position is “On.” Do

not change selection unless instructed to do so by

the factory.

-Slow Flash = 1 flash every 2 seconds
-Fast Flash = 2 flashes every 1 second
-Flash code 2 = 2 quick flashes, 10 second pause, 2 quick

flashes, 10 second pause, etc.

Description of Operation

LED

Alarm Relay

Normal Mode

On

Open

Normal Mode with UPS Warning

On

Cycle (closed 5 sec., Open 25 sec.)

CXM is non-functional

Off

Open

Fault Retry

Slow Flash

Open

Lockout

Fast Flash

Closed

Over/Under Voltage Shutdown

Slow Flash

Open (Closed after 15 minutes)

Test Mode - No fault in memory

Flashing Code 1

Cycling Code 1

Test Mode - HP Fault in memory Flashing Code 2

Cycling Code 2

Test Mode - LP Fault in memory Flashing Code 3

Cycling Code 3

Test Mode - FP1 Fault in memory Flashing Code 4

Cycling Code 4

Test Mode - FP2 Fault in memory Flashing Code 5

Cycling Code 5

Test Mode - CO Fault in memory Flashing Code 6

Cycling Code 6

Test Mode - Over/Under

shutdown in memory

Flashing Code 7

Cycling Code 7

Test Mode - UPS in memory

Flashing Code 8

Cycling Code 8

Test Mode - Swapped Thermistor Flashing Code 9

Cycling Code 9

Table 3a: CXM LED And Alarm

Relay Operations

Short test pins

together to enter

Test Mode and

speed-up timing

and delays for

20 minutes.

Figure 9: Test Mode Pins