Unit start up procedures, Warning – Comfort-Aire HWW120 User Manual

Page 26

Advertising
background image

25

Installation & Operation

WATER-TO-WATER (HWW) SERIES

Heat Controller, Inc.

Unit Start Up Procedures

Table 5: Water Temperature Change

Through Source Heat Exchanger

Note: Units have a five minute time delay in the control

circuit that can be eliminated on the CXM PCB as shown

in Figure 9 [Page 20]. See controls description for detailed

features of the control.

1. Adjust all valves to their full open position. Turn on the

line power to all heat pump units.

2. Operate each unit in the cooling cycle. Loop water

temperature entering the heat pumps should be be-

tween 70°F [21°C] and 110° F [43°C].

3. Operate each heat pump in the heating cycle imme-

diately after checking cooling cycle operation. A time

delay will prevent the compressor from re-starting for

approximately five (5) minutes.

4. Establish a permanent operating record by logging the

unit operating conditions at initial start-up for each unit.

5. If a unit fails to operate, conduct the following checks:

a. Check the voltage and current. They should com-

ply with the electrical specifications described on

the unit nameplate.

b. Look for wiring errors. Check for loose terminal

screws where wire connections have been made

on both the line and low-voltage terminal boards.

c. Check the supply and return piping. They must be

properly connected to the inlet and outlet connec-

tions on the unit.

d. If the checks described above fail to reveal the

problem and the unit still will not operate, contact

a trained service technician to ensure proper diag-

nosis and repair of the equipment.

� WARNING! �

When the disconnect switch is closed, high voltage is

present in some areas of the electrical panel. Exercise

caution when working with energized equipment.

� WARNING! �

Verify ALL water controls are open and allow water flow

prior to engaging the compressor. Freezing of the coax

or water lines can permanently damage the heat pump.

Water Flow, gpm [l/m]

Rise, Cooling

°F, [°C]

Drop, Heating

°F, [°C]

For Closed Loop: Ground Source or

Closed Loop Systems at 3 gpm per

ton [3.9 l/m per kW]

9 - 12

[5 - 6.7]

4 - 8

[2.2 - 4.4]

For Open Loop: Ground Water

Systems at 1.5 gpm per ton

[2.0 l/m per kW]

20 - 26

[11.1 - 14.4]

10 - 17

[5.6 - 9.4]