Safety features, Table 4: building commissioning – Comfort-Aire HWW120 User Manual

Page 23

Advertising
background image

22

Heat Controller, Inc.

WATER-TO-WATER (HWW) SERIES

Installation & Operation

Safety Features

c)

In cooling mode with compressor energized,

FP2 is less than 40°F [4.5°C] for 30 continuous

seconds.

If a UPS condition occurs, the control will immediately go to

UPS warning. The status LED will remain on as if the control

is in normal mode. Outputs of the control, excluding LED

and alarm relay, will NOT be affected by UPS. The UPS

condition cannot occur during a compressor off cycle. During

UPS warning, the alarm relay will cycle on and off. The cycle

rate will be “on” for 5 seconds, “off” for 25 seconds, “on” for

5 seconds, “off” for 25 seconds, etc.
UPS warning code = 8
Swapped FP1/FP2 thermistors: During test mode, the con-

trol monitors to see if the FP1 and FP2 thermistors are in the

appropriate places. If the control is in test mode, the control

will lockout with code 9 after 30 seconds if:

a)

The compressor is on in the cooling mode and

the FP1 sensor is colder than the FP2 sensor, or:

b)

The compressor is on in the heating mode and

the FP2 sensor is colder than the FP1 sensor.

Swapped FP1/FP2 thermistor code = 9.

Diagnostic Features

The LED on the CXM board advises the technician of the

current status of the CXM control. The LED can display

either the current CXM mode or the last fault in memory if in

test mode. If there is no fault in memory, the LED will flash

Code 1 (when in test mode).

CXM Control Start-up Operation

The control will not operate until all inputs and safety con-

trols are checked for normal conditions. The compressor will

have a 5 minute anti-short cycle delay at power-up. The first

time after power-up that there is a call for compressor, the

compressor will follow a 5 to 80 second random start delay.

After the random start delay and anti-short cycle delay, the

compressor relay will be energized. On all subsequent com-

pressor calls, the random start delay is omitted.

CXM Controls

Unit Commissioning & Operating Conditions

Environment – This unit is designed for indoor installation only.

Do not install in an area subject to freezing or where humidity

levels can cause cabinet condensation.
Power Supply – A voltage variation of +/- 10% of nameplate

utilization voltage is acceptable.
Operation and performance is primarily dependent upon water

temperatures, water flow rates and ambient air temperature. This

water to water heat pump is capable of operating over a wide

temperature range and with flow rates of between 1.5 GPM (.1

l/s) and 3 GPM (.19 l/s) per ton, however usually no more than

one of these factors may be at a minimum or maximum level at

a time.
The commissioning table indicates water temperatures which are

suitable for initial unit commissioning in an environment where

the flow rate and water temperature is not yet stable and to avoid

nuisance shut down of the units freeze and refrigerant pressure

safeties.
The operating Table 4 indicates the maximum and minimum

ranges of the unit.
For more specific unit performance reference the product

catalog, the submittal data sheets or contact your supplier for

assistance.

BUILDING COMMISSIONING

Cooling

Heating

Unit Size

036

060/120

036

060/120

Source Min/Max

50/110

50/120

30/80

30/80

Load Min/Max

60/80

60/90

60/120

60/120

Ambient Min/Max

45/110

39/85

BUILDING OPERATING

COOLING

HEATING

Unit Size

036

060/120

036

060/120

Source Min/Max

50/120

50/120

20/80

20/80

Load Min/Max

50/90

50/90

60/130

60/130

Ambient Min/Max

45/110

39/85

Table 4: Building Commissioning