Water-loop heat pump applications, Warning! � � caution, Figure 2: typical water-loop application – Comfort-Aire HWW120 User Manual

Page 10

Advertising
background image

9

Installation & Operation

WATER-TO-WATER (HWW) SERIES

Heat Controller, Inc.

Water-Loop Heat Pump Applications

Commercial systems typically include a number of units

plumbed to a common piping system. Any unit plumbing

maintenance work can introduce air into the piping system,

therefore air elimination equipment is a major portion of the

mechanical room plumbing. In piping systems expected to

utilize water temperatures below 50°F [10°C], 1/2” [13mm]

closed cell insulation is required on all piping surfaces to

eliminate condensation. Metal to plastic threaded joints should

never be employed due to their tendency to leak over time.

Teflon tape thread sealant is recommended for FPT water

connections (commercial class) to minimize internal fouling

of the heat exchanger. Do not overtighten connections and

route piping so as not to interfere with service or maintenance

access. Hose kits are available from Heat Controller in

different configurations for connection between the system.

The piping system should be flushed to remove dirt, piping

chips, and other foreign material prior to operation. See

Piping System Cleaning and Flushing Procedures later in this

document. The flow rate is usually set between 2.25 gpm and

3 gpm per ton [2.9 l/m and 4.5 l/m per kW] of cooling capacity.

Heat Controller recommends 2.5 gpm per ton [3.2 l/m per

kW] for most applications of water loop heat pumps. To insure

proper maintenance and servicing, P/T ports are imperative

for temperature and flow verification, as well as performance

checks. See Figure 2 for typical water-loop application

installation.

Cooling Tower/Boiler Systems typically utilize a

common loop maintained 60-90°F [16-32°C]. The use of a

closed circuit evaporative cooling tower with a secondary

heat exchanger between the tower and the water loop

is recommended. If an open type cooling tower is used

continuously, chemical treatment and filtering will be

necessary.

Low Water Temperature Cutout Setting

CXM Control: When an antifreeze is selected, the FP1

jumper (JW3) should be clipped to select the low temperature

(Antifreeze 15°F [-9.4°C]) setpoint to avoid nuisance faults.

See Figure 5: Low Water Temperature Cutout - FP1.

� WARNING! �

� CAUTION! �

Never jumper terminal “A” from CXM board #1 to CXM

board #2 on multi-compressor/control bound units. See

Figure 6 [Page 15] in electrical section of this document

for motorized valve wiring.

CAUTION! Many units are installed with a factory or

field supplied manual or electric shut-off valve. DAMAGE

WILL OCCUR if shut-off valve is closed during unit

operation. A high pressure switch must be installed on

the heat pump side of any field provided shut-off valves

and connected to the heat pump controls in series with

the built-in refrigerant circuit high pressure switch to

disable compressor operation if water pressure exceeds

pressure switch setting. The field installed high pressure

switch shall have a cut-out pressure of 300 psig and a

cut-in pressure of 250 psig.

Air Pad or

Extruded

polystyrene

insulation board

Unit Power

Disconnect

Thermostat Wiring

Load Plumbing

Connection

Optional

Balancing

Valve

Water Out

Optional Low

Pressure Drop

Water Control

Valve

Ball Valve with

integral P/T plug

Stainless steel braid

hose with integral “J”

swivel

Y-Strainer

with blow-off

valve

Water In

Ball Valve with

integral P/T plug

Building

Loop

Figure 2: Typical Water-Loop Application

Advertising
This manual is related to the following products: