Unit & System Checkout

UNIT CHECKOUT

q

Balancing/Shutoff Valves: Ensure all isolation

valves are open, water control valves wired and

open or coax may freeze and burst.

q

Line Voltage and Wiring: Ensure Voltage is within

an acceptable range for the unit and wiring and

fuses/breakers are properly sized. Low voltage

wiring is complete.

q

Unit Control Transformer: Ensure transformer has

properly selected control voltage tap. 208-230V

units are factory wired for 208V operation unless

specified otherwise.

q

Entering Water: Ensure entering water temperatures

are within operating limits of Table 6 [Page 25].

q

Low Water Temperature Cutout: Verify low water

temperature cut-out on CXM is properly set.

q

Water Flow Balancing: Verify inlet and outlet water

temperatures on both Load and source are record-

ed for each heat pump upon startup. This check can

eliminate nuisance trip outs and high velocity water

flows that can erode heat exchangers.

q

Unit Controls: Verify CXM field selection options

are proper and complete.

SYSTEM CHECKOUT

q

System Water Temperature: Check load and

source water temperature for proper range and

also verify heating and cooling setpoints for proper

operation.

BEFORE POWERING SYSTEM, please check the following:

q

System pH: System water pH is 6 - 8.5. Proper pH

promotes longevity of hoses and fittings.

q

System Flushing: Verify all hoses are connected

end to end when flushing to ensure debris bypass-

es unit heat exchanger and water valves etc. Water

used in the system must be potable quality initially

and clean of dirt, piping slag, and strong chemical

cleaning agents. Verify all air is purged from the

system. Air in the system can cause poor operation

or system corrosion.

q

Cooling Tower/Boiler: Check equipment for proper

setpoints and operation.

q

Standby Pumps: Verify the standby pump is prop-

erly installed and in operating condition.

q

System Controls: Verify system controls function

and operate in the proper sequence.

q

Low Water Temperature Cutout: Verify low water

temperature cut-out controls are provided for the

outdoor portion of the loop or operating problems

will occur.

q

System Control Center: Verify control center and

alarm panel for proper setpoints

and operation.

q

Strainers: Verify 20 mesh (841 micron) [0.84mm]

strainers are installed in load and source water pip-

ing. Confirm maintenance schedule for strainers.

q

Miscellaneous: Note any questionable aspects of

the installation.

� WARNING! �

Verify ALL water controls are open and allow water flow

prior to engaging the compressor. Freezing of the coax

or water lines can permanently damage the heat pump.

� WARNING! �

To avoid equipment damage, DO NOT leave system

filled in a building without heat during the winter unless

antifreeze is added to system water. Condenser coils

never fully drain by themselves and will freeze unless

winterized with antifreeze.

NOTE:

Heat Controller strongly recommends all piping

connections, both internal and external to the unit,

be pressure tested by an appropriate method prior to

any finishing of the interior space or before access

to all connections is limited. Test pressure may not

exceed the maximum allowable pressure for the

unit and all components within the water system.

Heat Controller will not be responsible or liable for

damages from water leaks due to inadequate or

lack of a pressurized leak test, or damages caused

by exceeding the maximum pressure rating during

installation.