Preventative maintenance – Comfort-Aire HWW120 User Manual

Page 30

Advertising
background image

29

Preventative Maintenance

Heat Exchanger Maintenance –

(Direct Ground Water Applications Only)
If the installation is performed in an area with a known high

mineral content (125 P.P.M. or greater) in the water, it is best

to establish with the owner a periodic maintenance schedule

so the coil can be checked regularly. Consult the well water

applications section of this manual for a more detailed water

coil material selection. Should periodic coil cleaning be

necessary, use standard coil cleaning procedures which are

compatible with either the heat exchanger material or copper

water lines. Generally, the more water flowing through the

unit the less chance for scaling therefore 2.5 gpm per ton

[2.0 l/m per kW] is recommended as a minimum flow.

Heat Exchanger Maintenance –

(All Other Water Loop Applications)
Generally water coil maintenance is not needed however,

if the installation is located in a system with a known high

dirt or debris content, it is best to establish with the owner a

periodic maintenance schedule so the coil can be checked

regularly. These dirty installations are a result of the dete-

rioration of iron or galvanized piping or components in the

system or open cooling towers requiring heavy chemical

treatment and mineral buildup through water use. Should

periodic coil cleaning be necessary, use standard coil clean-

ing procedures which are compatible with both the heat

exchanger material and copper water lines. Generally, the

more water flowing through the unit, the less chance for

scaling, however flow rates over 3 gpm per ton [3.9 l/m per

kW] can produce water (or debris) velocities that can erode

the heat exchanger wall and ultimately produce leaks.
Clean or replace 20 mesh (841 micron) [0.84mm] strainer/

filters on a timely schedule.

Compressors

Conduct annual amperage checks to ensure amp draw is

no more than 10% greater than that indicated by serial plate

data.

Cabinet

Do not allow water to stay in contact with the cabinet for long

periods of time to prevent corrosion of the cabinet sheet

metal. Generally vertical cabinets are set up from the floor a

few inches for prevention. The cabinet can be cleaned using

a mild detergent.

Refrigerant System

To maintain sealed circuit integrity, do not install service

gauges unless unit operation appears abnormal. Reference

the operating chart for pressure and temperatures. Verify

that air and water flow rates are at proper levels before ser-

vicing the refrigerant circuit.
If the refrigerant circuit is opened for any reason, a new

liquid line filter-drier must be installed.

Installation & Operation

WATER-TO-WATER (HWW) SERIES

Heat Controller, Inc.

Advertising
This manual is related to the following products: