Unit Installation

HWW Unit Location

These units are not designed for outdoor installation. Locate

the unit in an INDOOR area that allows enough space for ser-

vice personnel to perform typical maintenance or repairs.
The installation of water source heat pump units and all as-

sociated components, parts and accessories which make up

the installation shall be in accordance with the regulations of

ALL authorities having jurisdiction and MUST conform to all

applicable codes. It is the responsibility of the Installing Con-

tractor to determine and comply with ALL applicable codes and

regulations.

Locate the unit in an indoor area that allows easy removal of

access panels, and has enough space for service personnel

to perform maintenance or repair. Provide sufficient room to

make water and electrical connections.. Any access panel

screws that would be difficult to remove after the unit is in-

stalled should be removed prior to setting the unit. These units

are not approved for outdoor installation and, therefore, must

be installed inside the structure being conditioned. Do not

locate in areas where ambient conditions are not maintained

within 40-100°F [4-38°C].

Installation of Supply and Return Piping

Follow these piping guidelines.
1.

Install a drain valve at the base of each supply and

return riser to facilitate system flushing.

2.

Install shut-off / balancing valves and unions at each

unit to permit unit removal for servicing.

3.

Place strainers at the inlet of each system

circulating pump.

4.

Select the proper hose length to allow slack between

connection points. Hoses may vary in length by +2% to

-4% under pressure.

5.

Exceeding the minimum bend radius may cause the

hose to collapse which reduces water flow rate. Install

an angle adapter to avoid sharp bends in the hose

when the radius falls below the required minimum and

causes a slight kink.

Insulation is not required on loop water piping except where

the piping runs through unheated areas or outside the build-

ing or when the loop water temperature is below the minimum

expected dew point of the pipe ambient temperature. Insula-

tion is required if loop water temperature drops below the dew

point.
Pipe joint compound is not necessary when Teflon threaded

tape is pre-applied to hose assemblies or when flared-end

connections are used. If pipe joint compound is preferred,

use compound only in small amounts on the pipe threads of

the fitting adapters. Prevent sealant from reaching the flared

surfaces of the joint.
Note: When anti-freeze is used in the loop, assure that it is

compatible with Teflon tape or pipe joint

compound employed.
Maximum allowable torque for brass fittings is 30 ft-lbs [41

N-m]. If a torque wrench is not available, tighten finger-tight

plus one quarter turn. Tighten steel fittings as necessary.

Piping Installation

� WARNING! �

� WARNING! �

Piping must comply with all applicable codes.

Do not bend or kink supply lines or hoses.

Optional pressure-rated hose assemblies designed specifically

for use with Heat Controller units are available. Similar hoses

can be obtained from alternate suppliers. Supply and return

hoses are fitted with swivel-joint fittings at one end to prevent

kinking during installation.
Refer to Figure 1 for an illustration of a Supply/Return Hose

Kit. Male adapters secure hose assemblies to the unit and ris-

ers. Install hose assemblies properly and check them regularly

to avoid system failure and reduced service life.

� CAUTION! �

Corrosive system water requires corrosion resistant fittings

and hoses and possibly water treatment.

Figure 1: Supply/Return Hose Kit

Rib Crimped

Length

(2 ft [0.6m] Length Standard)

Swivel
Brass
Fitting

Brass

Fitting

EPT

Reborde Acanalado

Longitud

(Long. Estándar de 2 pies)

Accesorio
Giratorio
de Bronce

Accesorio
de Bronce

MPT

Gasket

Swivel Nut

Stainless steel

snap ring

Brass Adaptor

Hand Tighten

Only !

Do Not

Overtighten!