DuraVent PolyPro User Manual

Page 11

Advertising
background image

11

pipe is to be installed on the exhaust
outlet.

3. Once securely installed to exterior, verify

exhaust pipe cannot be removed from
termination cap.

Stainless Horizontal (Fig.16)
1. Cut opening in the wall.
2. Add Trim Plates and locking band (if

applicable) to final pipe length before
installing. Make sure flanges are facing
towards the wall. Use non-hardening
sealant where necessary.

3. After exterior trim plate is mounted to

wall, measure 3" from exterior plate and
cut off female pipe end. Duburr. Seal
pipe to exterior plate. Slide Bird screen
over cut pipe end and tighten clamp.

Figure 19

EXHAUST

AIR INLET

Figure 18

TERMINATION

CAP

FLASHING

STORM COLLAR

SUPPORT CLAMP

Figure 17

CENTERLINE OF

EXHAUST OUTLET

OF APPLIANCE

Vertical Concentric (Fig.18)
1. Locate penetration. (Fig.17)
2. Cut hole in roof. (Table 3)
3. Cut hole in ceiling above appliance.

Cut hole(s) big enough for pipe in all
ceilings above appliance if installing
in a multi story installation.

4. Firestop each ceiling penetration.
5. Attach flashing to roof. (Fig.18)

Slide storm collar onto flashing if
using the Adjustable Roof Flashing.

6. Slide vertical termination into flashing

from above until seated on flashing.

7. Plumb Termination and mount support

bracket to structure.

CUT LINE

THROUGH HOLE SIZING

4PPS: 4.125" 5PPS: 5.25"

6PPS: 6.125" 8PPS: 8.00"

EXTERIOR PLATE

INTERIOR PLATE

PP PIPE

INITIAL

FINAL

BIRD

SCREEN

CLAMP

FLANGES

Figure 16