DuraVent PolyPro User Manual

Page 7

Advertising
background image

INSTALLATION
1. Pipe lengths may be cut to length

(Fig.6). Use an alternate clamp (Fig.4-

PPS-PAC / PPS-LBC) for the connection

if a locking button (Fig.3) is removed.

Cut square (not at an angle) to the
end of the pipe.

Remove burrs before assembly.

Figure 6

MARK

CUT WITH

HACKSAW

DEBURR

7

Figure 7

12"

5/8"

MIN

1/4" - 5/8"

(7.5mm - 15mm)

TO APPLIANCE

2. Check with appliance manufacturer for

any restrictions or limits on vent length,
number of elbows, etc.

3. The slope of the vent pipe must be at

least 3° (5/8" per ft, 50mm per meter)
back to the appliance. (Fig.7)

4. Every horizontal section must be

supported. (Fig.8)

5. The venting system shall be securely

supported using suitable hangers.
Duravent hardware is recommended; field
supplied support hardware suitable to
the AHJ is acceptable, hardware must not
deform or damage the vent. (Fig. 7 and 8)
Make sure the load of the vent system is not
supported by the appliance.

On Duravent and other certain clamp
styles, ¼” or greater All-thread may be
used as an extension.

6. Vertical installations must be supported

every 10 feet (3 meters) or less. (Fig.8)

7. Do not install / enclose PolyPro in the stud

space of a wall.

8. Elbows and Tees are sufficiently supported

when a bracket is fixed at the female end of
the connected straight section. (Fig.8)

PP Pipe sections must be disengaged 1/4"-

5/8" per joint (to allow for expansion) and

sloped 3°(5/8"per ft) back to the appliance

per Fig.7 for proper condensate flow.

IMPORTANT

Figure 8

ALL-THREAD

WALL STRAP

(MINIMUM 1PER

HORIZONTAL PIPE

SECTION)

LOCKING BANDS

REQUIRED AT EVERY

EXHAUST JOINT

MAX

10FT

(3m)

9. Vertical components can be insulated in

unconditioned space or when ran outside.

10. Use black UV protected components on

venting installed on the exterior.

ENCLOSURE REQUIREMENTS

Through Rooms: Interior vents shall be
enclosed where they extend through closets,
storage areas, occupied spaces, or anyplace
where the surface of the vent could be
contacted by persons or combustible materials
except when installed in the room with the
appliance.