IMPORTANT

To prevent possible recirculation of flue

gases, the installer must consider the

effects of prevailing wind conditions,

eddy zones, nearby buildings,

obstructions, or other obstacles such as

shrubs when planning exhaust and air

intake locations. M&G DuraVent can not

be held responsible for poor appliance

performance or damage to buildings

due to an incorrect installation. The

minimum clearances detailed within our

instructions may not be adequate in some

circumstances depending on the specifics

of the installation. For this reason we

always recommend vertical venting.

JOINT CONNECTIONS
Verify the gasket is seated evenly inside the
groove in the female end. There are two
versions of locking band available, one with
standoff legs (Fig.2), one without (Fig.3).
For both: Slide Locking Band on male pipe
section. Fig.2: For pipe without Locking
Button: Slide pipe sections together until
joint is bottomed out then slide apart ¼”
to 5/8” (7.5 - 15 mm) for expansion. Clip the
locking band clasp onto the female hub.

Fig.3: For PP/Metal pipe with Locking Button:
Insert locking button into locking band
recess, rotate button away from Locking
Band Clasp, insert pipe sections, push
lock band clamp downward into socket,
disengage button 1/4" from socket. Screws

are not allowed for joint connection.

Never penetrate the wall of PolyPro vent

pipe. (Exception- a SS screw may be

used outside the building on exterior

termination fittings to orient an elbow,

etc).

IMPORTANT: Locking bands are

Figure 1

SIPHON

Table 2 - Equivalent Length Chart

2" Equivalent

Length

3" Equivalent

Length

4" Equivalent

Length

5" Equivalent

Length

6" Equivalent

Length

8" Equivalent

Length

1-ft Vent Pipe

1-ft

1-ft

1-ft

1-ft

1-ft

1-ft

1-ft Flex Pipe

2-ft

(same diameter

as rigid)

2-ft

(same diameter

as rigid)

2-ft

(same diameter

as rigid)

2-ft

(same diameter

as rigid)

N/A

N/A

1-ft Flex Pipe

0.4-ft

(updsized one

diameter)

0.6-ft

(updsized one

diameter)

0.6-ft

(updsized one

diameter)

N/A

N/A

N/A

45 Elbow

3-ft

3-ft

5-ft

6-ft

6-ft

13-ft

90 Elbow

5-ft

7-ft

12-ft

14-ft

14-ft

19-ft

Tee

9-ft

12-ft

19-ft

21-ft

22-ft

29-ft

WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow these installation

instructions could result in personal

injury or death

P-TRAP