7 program number table, Program number table – WIKA DI30 User Manual

Page 30

Advertising
background image

6 Commissoning, operation

30

WIKA operating instructions digital indicator DI30

6.7 Program number table

The program table lists all the program numbers (PN) with their function,
range of values, default values and user level.

PN

Function

Range of value

De-
fault

User
level

0

Measuring input

Parameters 1 to 4 make
use of the factory
calibration.

Current, Voltage:
0 = Sensor calibration
1 = 0 ... 20 mA
2 = 4 ... 20 mA
3 = 0 ... 10 V
4 = 0 ... 5 V

2

2

1

Scaling final value

-999 ... 9999

1000

2

2

Scaling starting value

-999 ... 9999

0

2

3

Number of decimal places

0 = 0
1 = 0.0
2 = 0.00
3 = 0.000

0

2

5

Offset shift on display
value

-999 … 9999

0

2

10

Zero point suppression

0 … 999

0

2

General settings
13

Indication time

0.1 ... 10.0

1,0

2

14

Measuring time

0.01 ... 10.0

0.1

2

Security settings
50

Access code

0000 ... 9999

0000

8

51

Locking code

0000 ... 9999

0000

0

52

User level

1 ... 8

8

0

Function of the zero key
54

Actuator via zero key

0 = deactivated
1 = TARA
2 = Offset shift
3 = HOLD

0

2

Flashing of the LED-display
59

Display flashing (approx.
0.5 seconds)
No flashing
Flashes at alarm 1
Flashes at alarm 2
Flashes at alarm 1 and 2



0 = no flashing
1 = flashes at 1
2 = flashes at 2
3 = flashes at 1 and 2

0

4