WIKA DI30 User Manual

Page 31

Advertising
background image

6 Commissoning, operation

WIKA operating instructions digital indicator model DI30

31

PN

Function

Range of value

De-
fault

User
level

Alarm output 1
60

Alarm output 1

0 = deactivated
1 = activated

1

4

61

Threshold

-999 ... 9999

1000

6

62

Hysteresis

1 ... 9999

1

5

63

Active below / above
threshold value

0 = active below
1 = active above

1

4

64

Switch delay

0 … 1000 seconds

1

4

65

Delay type

0 = none
1 = switch-on delay
2 = switch-off delay
3 = switch-on/-off delay

0

4

Alarm output 2

70

Alarm output 2

0 = deactivated
1 = activated

1

4

71

Threshold

-999 ... 9999

1000

6

72

Hysteresis

1 ... 9999

1

5

73

Active below / above
threshold value

0 = active below
1 = active above

1

4

74

Switch delay

0 … 1000 seconds

1

4

75

Delay type

0 = none
1 = switch-on delay
2 = switch-off delay
3 = switch-on/-off delay

0

4

Linearisation
100

Number of additional
setpoints

0 ... 10

0

2

101...
110

Setpoints 1 ... 10

-999 ... 9999

2

Information
200

Serial number

0 ... 9999

0

8



Advertising