Bryant DURAPAC 579F User Manual

Page 12

Advertising
background image

12

Table 5 — Electrical Data

LEGEND

*Fuse or HACR circuit breaker.

NOTES:
1. In compliance with NEC requirements for multimotor and combina-

tion load equipment (refer to NEC Articles 430 and 440), the overcur-
rent protective device for the unit shall be fuse or HACR breaker.
Canadian units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent
of voltage imbalance.
% Voltage Imbalance

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact the local electric utility company immediately.

UNIT
579F

NOMINAL

VOLTAGE

(3 Ph, 60 Hz)

VOLTAGE

RANGE

COMPRESSOR

OFM

IFM

POWER

EXHAUST

COMBUSTION

FAN MOTOR

POWER

SUPPLY

No. 1

No. 2

Min Max RLA LRA RLA LRA Qty Hp

FLA

(ea)

Hp

FLA

FLA LRA

FLA

MCA

MOCP*

180

(15 Tons)

208/230

187

253

25.6

190

25.6

190

3

0.5

1.7

3.7 10.5/11.0

0.57

74/74

90/ 90

4.6

18.8

0.57

78/79

100/100

460

414

508

13.5

95

13.5

95

3

0.5

0.8

3.7

4.8

0.30

38

50

2.3

6.0

0.30

40

50

216

(18 Tons)

208/230

187

253

33

237

23

184

3

0.5

1.7

5.0 15.8/15.8

0.57

85/85

110/110

4.6

18.8

0.57

90/90

110/110

460

414

508

16.2

130

10.2

90

3

0.5

0.8

5.0

7.9

0.30

41

50

2.3

6.0

0.30

43

50

240

(20 Tons)

208/230

187

253

33

237

29.5

237

2

1

6.6

7.5 25.0/25.0

0.57

109/109 125/125

4.6

18.8

0.57

114/114 125/125

460

414

508

16.2

130

14.1

130

2

1

3.3

7.5

13.0

0.30

54

70

2.3

6.0

0.30

56

70

300

(25 Tons)

208/230

187

253

47.5

265

33.0

237

2

1

6.6

10.0 28.0/28.0

0.57

134/134 175/175

4.6

18.8

0.57

135/135 175/175

460

414

508

22.9

145

16.2

130

2

1

3.3

10.0

14.6

0.30

66

80

2.3

6.0

0.30

68

90

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code, U.S.A.

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

=

457

% Voltage Imbalance = 100 x

7

457

= 1.53%

Advertising